- ページ 19

産業機器 Siemens UL 508AのPDF リファレンス・マニュアルをオンラインで閲覧またはダウンロードできます。Siemens UL 508A 30 ページ。

4.2 SB4.3 – Adaptation of the available short-circuit current rating based on the peak let-through currents when
using current-limiting devices in the feeder circuit
Short-circuit current rating (SCCR) of industrial control panels
Reference Manual, 06/2013, A5E31896849002A/RS-AA/001
Basic steps for calculating the SCCR of a control panel
The selected circuit breaker lets 22 kA
through at a short-circuit of 100 kA.
⇒ In other words, all components in the
branch circuit must be designed for at
least 22 kA. The control panel is suitable
for a maximum let-through value of
100 kA.
19