APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor
Address
NGT DBAND
88
MORN DBAND
89
SWITCH DBAND
90
AUX DSH STPT
91
CTL STPT
92
DISCH STPT
93
MA STPT
93
DSH MIN TEMP
94
DSH MAX TEMP
95
LOOP TIME
98
ERROR STATUS
99
30
Application
2281, 2283,
During night mode, this point indicates the number of degrees
2284, 2286,
above or below (depending on heating/cooling mode) the night
2287
setpoint that the room temperature can raise or drop before the
fan will be turn ON.
Valid input: 0 to 255°F
2281, 2283,
The number of degrees of variance from the heating or cooling
2284, 2286,
setpoint at which the controller will terminate morning warm-up or
2287
cool-down and begin normal operation.
Valid input: 0 to 255'F
2281, 2283,
The temperature range in degrees that is compared to the
2284, 2286,
difference between CTL TEMP (Point 78) and CTL STPT (Point
2287
92). The difference exceeding this value is one of the conditions
necessary to change modes between heating and cooling.
Valid input: 0 to 255°F
2281, 2284
The setpoint of the auxiliary radiation control loop.
2281, 2283,
The actual setpoint value being used as input for the active
2284, 2286,
temperature control loop.
2287
2281, 2284,
The setpoint of the discharge air control loop.
2287
2283, 2286
The setpoint of the mixed air control loop.
2281, 2284
The minimum value to which DISCH STPT (Point 93) can be set
by the room control loop.
2281, 2284
The maximum value to which DISCH STPT (Point 93) can be set
by the room control loop.
2281, 2283,
The time, in seconds, between control loop calculations.
2284, 2286,
2287
2281, 2283,
The status code indicating any errors detected during controller
2284, 2286,
power up. A status of 0 indicates there are no problems.
2287, 2299
Description
Siemens Building Technologies, Inc.