Address
Descriptor
56
ODP STPT SW
57
RIGHT SW
63
FLOW P GAIN
64
FLOW I GAIN
66
FLOW D GAIN
67
FLOW BIAS
68
CTRL LOOPOUT
87
FLOW HI STPT
89
HORN
91
BLANK DSPLY
92
DO2 INVERTER
93
ENG UNITS
94
LAMP TEST
96
ALARM TIME
97
DUCT AREA
98
LOOP TIME
99
ERROR STATUS
Siemens Building Technologies, Inc.
Indicates if the lower left button on the ODP has been pressed. This is a toggle
action digital input; when pressed, the controller changes between HI and LOW
flow setpoints.
Indicates if the right auxiliary button on the ODP has been pressed. This is a
toggle action digital input; when pressed, the point is ON. If pressed again, the
point is OFF.
The proportional gain value for the fume hood flow control loop.
The integral gain value for the fume hood flow control loop.
The derivative gain value for the fume hood flow control loop.
The bias, in percent, of the fume hood flow control loop.
Control output of the flow loop. Range: -100% to 100%.
The hi flow setpoint used in FLOW STPT.
When this point is set to DISABLE, the audible alarm will not sound. All other
alarm functionality is still operational.
When set to YES, the exhaust flow is not displayed at the ODP.
Setting to NCLOSE allows the controller to operate industry standard floating
control actuators. Setting this point may stop the failsafe operation from
functioning.
Toggles the display of the ODP from CFM to LPS. Toggling this point does not
change the displayed value at the portable operators terminal.
Turns on all lights, prompts, and the audible alarm at the ODP.
Time delay for the red and yellow alarm LEDs used to eliminate sudden changes
and false alarms. The exhaust flow must rise above any of the set limits (for
example, HI ALM LMT) for the amount of time specified at this point before the
ODP indicates an alarm condition.
Area of the duct, in square feet (SQM), where the air velocity sensor is located.
The time, in tenths of a second, between control loop calculations.
The status code that indicates any errors detected during controller power-up.
Description
Point Database
19