- ページ 5
コントローラー Siemens 18のPDF 交換部品と取扱説明書をオンラインで閲覧またはダウンロードできます。Siemens 18 6 ページ。 Combination starters
Replacement Parts and Instruction Guide
Instruction Guide
Notes: Toggle on circuit breaker must
fit through notch in pivot assembly.
Circuit Breaker Assembly Instructions
1.
Remove the two screws that connect the handle link to the
pivot assembly.
2.
Use a 5/16" wrench to remove the two 1/4-20 screws and
lock washers which secure the handle to the enclosure
flange. These screws are located on the underside of the
enclosure flange. Remove the old handle assembly from
the enclosure.
3.
Remove the lever assembly from the panel and replace it
with one provided. The mounting panel may need to be
removed to access the mounting screws.
4.
Hardware has been provided to mount a new circuit breaker
if necessary.
Siemens Industry, Inc. 3617 Parkway Ln, Peachtree Corners, GA 30092 www.usa.siemens.com
Circuit Breaker Handle Replacement Diagram *
5.
6.
7.
8.
9.
10. Manually trip the circuit breaker and verify that the handle
11. Verify that the door cannot be opened with the handle in
* Diagram applies to size 3.5 or 4 starters with E or F frame breaker
Install the new handle assembly onto the enclosure.
Reinstall the two 1/4-20 screws and lock washers. Make sure the
handle housing is sealed against the enclosure flange as this prevents
the entry of moisture.
Reinstall the two screws that connect the handle link to the
pivot assembly.
No handle adjustment is required.
Verify that the handle mechanism turns 'ON' and 'OFF' the
circuit breaker.
will reset the breaker.
the 'ON' position.
E87010-A0137-T003-A4
5
A5E31166526A-003