- ページ 7

コントローラー Siemens 3VT9500-3MQ10のPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Siemens 3VT9500-3MQ10 7 ページ。 Motorized operating mechanism with spring energy store

Siemens 3VT9500-3MQ10 取扱説明書
WARNING!
Motor drive handling
The circuit Breaker in revision posititon:
Removal of the motor drive from the cicuit breaker:
1. Disconnect the OD-BL-KA01 connector, or wiring from the motor drive.
2. Select Manual mode on the motor drive.
3. Pull on the lever of the drive spring mechanism.
4. Remove the motor drive from the circuit breaker.
Installation of the motor drive on the circuit breaker:
1. Pull on the circuit breaker lever (until this is pulled on from the previous cycle)
2. Select the manual mode on the motor drive and pull on the lever (drive spring mechanism)
3. Put the motor drive on the circuit breaker
4. Switch on the circuit breaker by means of the green button on the front side of the motor drive
5. Trip the circuit breaker by means of TEST button
6. Slide the circuit breaker from the revision to the working position
7. Change the motor drive mode from "AUTO" to "MANUAL" (if this is required and unless it has already been made.)
8. Connect the OD-BL-KA01 connector or wiring of the motor drive. When the green light "ACTIVE" is on, the whole assembly is ready for use.
When the red light "RESET MO" is on, the drive has to be restarted by disconnecting and re-connecting the power supply
The Circuit breaker in working position
Removal of the motor drive from the cicuit breaker:
1. Disconnect the OD-BL-KA01 connector or wiring from the motor drive.
2. Select Manual mode on the motor drive.
3. Pull on the lever of the drive spring mechanism.
4. Remove the motor drive from the circuit breaker.
Installation of the motor drive on the circuit breaker:
1. Pull on the circuit breaker lever (until this is pulled on from the previous cycle)
2. Select the manual mode on the motor drive and pull on the lever (drive spring mechanism)
3. Put the motor drive on the circuit breaker
4. Change the motor drive mode from "MANUAL" to "AUTO" (if this is required and unless it has been done already.)
5. Connect the OD-BL-KA01 connector or wiring of the motor drive. When the green light "ACTIVE" is on, the whole assembly is ready for use
When the red light "RESET MO" is on, the drive has to be restarted by disconnecting and re-connecting the power supply
Technische Änderungen vorbehalten. Zum späteren Gebrauch aufbewahren.
Subject to change without prior notice. Store for use at a later date.
!
Bestell-Nr./Order No.: 3ZX1012-0VT05-3NA1
A5E01467856-03 / 990547S00
© Siemens AG 2007