コントローラー Siemens 550-507のPDF 取付説明書をオンラインで閲覧またはダウンロードできます。Siemens 550-507 9 ページ。 Ce compliant dual duct controller -two air velocity sensors -electronic output

CE Compliant Dual Duct Controller — Two Air
Velocity Sensors — Electronic Output
Product Description
These instructions explain how to field install or
replace a CE Compliant Dual Duct Controller — Two
Air Velocity Sensors — Electronic Output with or
without Autozero Modules.
Shipping carton includes a controller assembly
(controller board and cover), a mounting rail, Autozero
Modules with brackets (optional), and two self-tapping
screws.
For CE compliance, ferrite filter(s) and an alternate
room sensor cable must be used (see Product
Numbers).
NOTE: Keep the controller assembly in its static-proof
bag until installation.
Product Numbers
Product
550-506
Dual Duct Controller — Two Air Velocity
Sensors — Electronic Output
550-507
Dual Duct Controller — Two Air Velocity
Sensors — Electronic Output with Autozero
Modules
588-100A
2-RJ11 room
588-100B
temperature
sensor cable
588-100C
550-705
clamp-on ferrite filter 10 pack
Caution Notation
CAUTION:
Description
25-ft (7.6-m)
50-ft (15.2-m)
100-ft (30.48-m)
Equipment damage or loss of
data may occur if the user
does not follow procedure as
specified.
Installation Instructions
Required Tools
Electro-Static Discharge (ESD) wrist strap
Small flat-blade screwdriver
Medium flat-blade screwdriver
Medium-duty electric drill
1/4-inch (6.35 mm) hex nut bit
Portable Operator's Terminal with Controller
Interface Software (CIS) Rev. 2.0 or higher
(controller replacement only)
Additional tools needed if not using self-tapping
option:
1/4-inch (6.35 mm) hex nut driver
1/8-inch (3 mm) bit
Prerequisites
Room temperature sensor installed (optional)
Air velocity sensors installed in ducts
24 Vac Class 2 power source
Supply power to the unit is OFF
Autozero Modules with brackets are on hand
(optional)
If required, controller enclosure installed
Expected Installation Time
New controller installation
Replacement with removable terminal
blocks
Replacement without removable
terminal blocks
NOTE: You may require additional time for
database work at the field panel.
Document No. 550-308
Rev. 1, July, 2001
10 min.
6 min.
16 min.
Page 1 of 9