コントローラー Siemens SQM53.464R1Z3のPDF テクニカル・インストラクションをオンラインで閲覧またはダウンロードできます。Siemens SQM53.464R1Z3 31 ページ。 Reversing
Siemens SQM53.464R1Z3 にも: テクニカル・インストラクション (31 ページ), テクニカル・インストラクション (31 ページ)
SQM5... Reversing Actuators
Switch Adjustment,
Continued
Shaft Adjustment
See Figure 6.
Cam Drum Adjustment
See Figure 6.
Position Indicating Dial
Adjustment
Wiring
Electrical Connection
Grounding
Siemens Building Technologies, Inc.
NOTE:
If a potentiometer is installed, the adjustable range of the switches depends
on the range of the potentiometer.
SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°.
SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be
adjusted only between 0 and 90°.
SQM5x.xxxxxx4 actuators have a 135° potentiometer and the switches must
be adjusted only between 0 and 135°.
The actuator shaft can be disengaged by pressing the silver shaft release button. The
button is located above the grounding screw, under the hinged terminal protection
cover, and to the right of the auto/manual switch. After pressing the shaft release button
in and slightly upward, the shaft can be manually rotated. After the shaft has been
manually aligned to the closed position, re-engage the shaft by pushing the shaft
release button downwards.
Once the shaft has been set, the cam drum must be manually aligned by pressing and
holding the black cam drum release button (see Figure 6). Rotate the cam drum until
the "0" mark on the actuator position scale (left scale on the cam drum) is aligned with
the gray actuator position indicating pointer.
The actual position of the SQM5... actuator is indicated by the gray actuator position
indicating pointer (see Figure 6). The position is also displayed by the indicating dial
through the housing's window. Ensure that the actuator position indicating dial is
aligned with the actuator position scale. If necessary, rotate the dial in the clockwise
direction.
CAUTION:
Turning the dial in the counterclockwise direction may loosen the
potentiometer locking screw.
SQM5... actuators are equipped with two removable conduit connection plates located
on the upper corner of the gear housing. Each plate is provided with two threaded
connections for 1/2" NPSM conduit connectors. The use of flexible stranded wire is
recommended.
CAUTION:
To avoid electro-magnetic interference, the SQM5... actuators must be
grounded.
The ground terminal is located to the right of the auto/manual switch.
Disconnect the circuit board wire marked 51 during high voltage testing.
Reconnect it to the grounding terminal after the test.
Technical Instructions
Document No. 155-517P25
July 9, 2007
Page 9