- ページ 17
コントロールユニット Siemens 2AI 2/4WIRE HFのPDF マニュアルをオンラインで閲覧またはダウンロードできます。Siemens 2AI 2/4WIRE HF 28 ページ。
Analog value representation
4.1
Introduction
Electronic modules with analog outputs
With the electronic module with analog inputs, continuously variable signals, such as those
occurring in temperature measurement and resistance measurement, can be acquired,
evaluated, and converted to digital values for further processing.
4.2
Analog value representation for measuring range with SIMATIC S7
Analog value representation
With the same nominal range, the digitized analog value is the same for input and output
values. Analog values are represented in two's complement.
The following table shows the analog value representation of the analog electronic modules.
Table 4-1
Analog value representation (SIMATIC S7 format)
Resolution
Bit number
Significance of the bits
Sign
The sign (S) of the analog value is always in bit number 15:
● "0" → +
● "1" → –
2 AI I 2/4WIRE HF analog electronic module (6ES7134-4MB02-0AB0)
Manual, 04/2007, A5E01076111-01
15
14
13
12
S
2
2
2
14
13
12
Analog value
11
10
9
8
7
2
2
2
2
2
11
10
9
8
6
5
4
3
2
2
2
2
7
6
5
4
3
4
2
1
0
2
2
2
2
1
0
17