コントロールユニット Siemens XC1001-AのPDF オペレーションをオンラインで閲覧またはダウンロードできます。Siemens XC1001-A 32 ページ。 Extinguishing control unit

Siemens XC1001-A オペレーション
Indicators
State
N° Color
14
Yellow
Fixed
15
Yellow
Fixed
16
Yellow
Fixed
17
Red
Fixed
Fast
18
Red
Fixed
Slow / Fast
19
Yellow
Fixed
Slow
Fast
20
Yellow
Fixed
Slow
Fast
21
Yellow
Fixed
Slow
Fast
22
Yellow
Fixed
Slow
23
Yellow
Fixed
Slow
Fast
24
Yellow
Fixed
Slow
Fast
25
Red
Fixed
Slow
26
Yellow
Fixed / Slow
Fast
27
Red
Fixed
Slow
28
Yellow
Fixed / Slow
Fast
29
Red
Fixed
Slow
30
Yellow
Fixed / Slow
Fast
31
Red
Fixed
Slow
32
Yellow
Fixed / Slow
Fast
Building Technologies
Fire Safety
Description
Manual release is blocked or being tested
Standard = not used
Alternative = automatic and manual release granted (UK)
Automatic release is blocked
At least one detection zone which starts the extinguishing is off or being tested
All detection zones which start the extinguishing are in alarm condition
One of the electrical manual triggering device (DM1103-L) is actuated
One of the detection zones which start the extinguishing is in alarm condition
Extinguishing agent is released
Discharged contact is not activated within 30 seconds after actuators control
Sounders are disabled
Sounders test is in progress (real activation)
At least, an output programmed as Sounders is in fault condition (break or short-circuit)
Actuators are disabled
Actuators test is in progress (simulated activation)
At least, one output programmed as actuators is in fault condition (break or short-circuit)
Calibration in progress or error or no calibration data
Fire controls are disabled
Warning panels test is in progress (real activation)
At least, one output programmed as fire controls is in fault condition (break or short-circuit)
RT-fault is disabled
RT-fault test is in progress (real activation)
RT-alarm is disabled
RT-alarm test is in progress (real activation)
At least, one output programmed as RT-alarm is in fault condition (break or short-circuit)
Emergency abort is activated
Emergency hold is activated (DM1101-S)
At least, one input programmed as emergency hold/abort is in fault condition (break or short-circuit)
Detection zone 1 is in alarm condition
Detection zone 1 is in alarm condition (first alarm)
Detection zone 1 is disabled (fixed) / being tested (slow)
Detection zone 1 is in fault condition (break or short-circuit)
Detection zone 2 is in alarm condition
Detection zone 2 is in alarm condition (first alarm)
Detection zone 2 is disabled (fixed) / being tested (slow)
Detection zone 2 is in fault condition (break or short-circuit)
Detection zone 3 is in alarm condition
Detection zone 3 is in alarm condition (first alarm)
Detection zone 3 is disabled (fixed) / being tested (slow)
Detection zone 3 is in fault condition (break or short-circuit)
Manual release is activated (DM1103-L line)
Manual release is activated (DM1103-L line) – First alarm
Manual release is disabled (fixed) / being tested (slow)
Manual release is in fault condition (break or short-circuit)
Operation
17
A6V10257477_c_en_--
2012-06