5.4.3
Blocking remote transmission of activation of extinguishing and fault
Building Technologies
Fire Safety & Security Products
This function may be inoperable.
If, in exceptional cases, alarm or fault shall not be remotely transmitted, remote
transmission of the alarm or the fault must be blocked.
Blocked remote transmissions are also not activated in the event of an alarm or
WARNING
a fault! Therefore, enable blocked remote transmission again as soon as normal
conditions prevail!
Here's how to proceed, in order to block remote transmission:
1. Enable "Access level 2".
The LED "Operating access" lights up.
2. Press the "Disable/Enable" key ("RT-alarm"/"RT-fault") until the desired blocking
is displayed. After blocking, you can proceed with the desired work.
The first pressing blocks the remote transmission of faults:
–
The yellow LEDs "RT-fault"/"Disabled" light up.
The second pressing blocks the remote transmission of alarm:
–
The yellow LEDs "RT-alarm"/"Disabled" light up.
The third pressing blocks the remote transmission of fault and alarm:
–
The yellow LEDs "RT-fault"/"RT-alarm"/"Disabled" light up.
The fourth pressing re-enables the remote transmission of fault and alarm:
–
The yellow LEDs "RT-fault"/"RT-alarm"/"Disabled" are no longer lit.
3. The system is again in normal operation.
Operation
21
A6V10099835_a_en
12.2007