Fig. 34
Cleaning the contact surfaces of the poles
9229 0098 176 0-
2019-01-09
Preparing contact surfaces
Note
Clean silver-plated contact areas with a cloth; do not brush.
Different connection materials (AI/Cu) must not be cleaned with the same clean-
ing tools.
Silver-plated parts must not be bolted to aluminium bars!
Use a steel brush to carefully brush (cross-wise) the contact surfaces of the cable
lugs or busbars until they are metallic bright and wipe off any residue using a clean
cloth.
After cleaning, very lightly grease the bright contact areas with acid-free Vaseline
(e. g. Shell-Vaseline 8420) and screw together immediately.
Fig. 35
Cleaning the contact surfaces of the busbars
Installation