Electronics and terminal
compartment
Wiring plan
*7ML19985KY01*
4. Insert the cable into the sensor through the cable entry
5. Open the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
7. Tighten the terminals with a screwdriver
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
10. Screw the housing lid back on
The electrical connection is finished.
5.3
Wiring plan, single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d
version.
7
6
5
Fig. 10: Electronics and terminal compartment, single chamber housing
1
Control lamp
2
DIL switch for characteristics reversal
3
DIL switch for sensitivity adjustment
4
Ground terminal
5 EMC filter element
6
Simulation key
7
Connection terminals
For connection of the amplifier according to NAMUR (IEC 60947-5-6,
EN 50227). You can find further information in the "Technical data".
SITRANS LVL200E - Operating Instructions
SW E60N Ex
N A M U R
( I E C 6 0 9 4 7 - 5 - 6 )
+ -
0,5 g / cm 3
M a x .
S i m u l .
0,7 g / cm 3
M i n .
1
2
3
4
19