- ページ 11
リレー c3controls 900 SeriesのPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。c3controls 900 Series 17 ページ。 Smart programmable relays
PROGRAMMING USING SPR-SOFT III SOFTWARE
SPR-soft III is the exclusive programming software for the Series 900 relay using Windows®. It facilitates:
ENTERING THE PROGRAM: SELECT & PLACE
SPR-soft III provides a user-friendly interface wherein the user has to only
select contact type and contact number and place it where it is required.
Contacts get connected automatically if they are on the same line. User can
enter comments for better readability and for future reference.
SAVING PROGRAMS
SPR-soft III allows user to save individual programs on the PC.
DEBUGGING
SPR-soft III is very powerful in error handling. It displays any possible errors as
the program is being entered to make corrections simultaneously.
SIMULATION ON PC
User can simulate the program on a PC. User can use buttons provided on the
screen to simulate the input connections. Scroll bar can be used to simulate
Analog input. The actuation / de-actuation of the relays can be monitored on
the screen.
SIMULATION ON THE SERIES 900 RELAY
User can connect the Series 900 relay unit to a PC using a serial Communication
cable / USB cable and perform on line program simulation. In this mode the PC
acts as a master and the inputs are taken from the Series 900 relay and outputs
are sent to the Series 900 relay unit (and the expansion modules, if connected).
This mode is useful in debugging the entire system since the actual I/Os are
used.
PRINTING
User can take print outs of programs in two different formats, namely Short
format and Detail format. Also, program Parameters and Comments can be
printed.
TRANSFERRING PROGRAMS
Programs can be transferred from a PC to the Series 900 relay and vice-versa
using serial Communication cable / USB cable. This saves the program entering
time on the Series 900 relay.
TRANSFERRING CLOCK
With this utility user can set the clock (date and time) on the Series 900 relay.
Series 900 SPR-soft III
Program Editor
Window
Input/Ouput
Window
Error Window
LIFETIME WARRANTY
GUARANTEED SAME-DAY SHIPPING
ADVANTAGE PRICING
CREATING A NEW PROGRAM
Select File -> New from the menu bar to create a new program.
A blank screen will appear. Now you can start entering the program. Ensure
that you have chosen the proper Series 900 relay Configuration before starting
the program entry.
CHOOSING CONTACT TYPE
Position the cursor at the place where you want to insert the contact by
a left click with the mouse. The position will get highlighted. Choose the
required contact type and Contact Number from I/O function selector. Click
on the required contact and contact number, which will be highlighted for
a few seconds. The selected contact will appear at the position selected in
the program. The selected contact number will be shown with a tick mark to
indicate that it has been used in the program. You can right click on any of the
contacts to change its type and properties.
CONNECTING INPUTS & OUTPUTS
Each circuit connection runs from left to right. Please remember this when
you interconnect contacts and relay coils. User can draw a circuit connection
horizontally from left to right and vertically between adjacent circuit
connections. An intersection of circuit connections represents an electrical
connection.
HORIZONTAL CONNECTION
To make a horizontal connection, click on the horizontal dotted line in the
connection box of the circuit. Or to make a connection in the contact box,
press the right button and select "Joining Link". Generally when an output coil
is placed in the fourth column, it gets automatically connected.
VERTICAL CONNECTION
To make a vertical connection click on the vertical dotted line in the connection
box of the circuit. Vertical connection represents OR connection. For deleting a
connection, left click on the connection line.
11
I/O Function
Selector Window