Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Operation and connection of Manual Control Points
The Manual Control Point will generally contain the following:
• Breakable glass window and red control button is activated by
pressure - this puts the control panel in ALARM condition, by
which the motor output is activated (for normal service and testing
the lid can be opened with a key).
• RESET button which brings the control panel out of the alarm
condition and starts the closing sequence for about 180 seconds.
Please note that RESET does not cancel errors on the system, e.g.
line errors etc. These must be found and corrected.
• RED LED indicates that the control panel is in ALARM condition
and that the motor output either is or has been activated.
• YELLOW LED indicates faults on the system - please call for a
service technician.
• GREEN LED indicates that the system is in normal operation
condition without errors.
CONNECTION of the fire switch is made as shown on the drawing.
The installation with fire switches must be terminated with a 10KΩ or
27KΩ resistor in the last switch in order to establish the line monitoring
correctly – this can either be done by moving the factory mounted resistor
from the terminal strip to the last fire switch or connect jumper J1 in
the fire switch type BVT is mounted (by this a 10KΩ resistor is also
connected).
By means of DIP switches the control panel has different possibilities of
settings for the input to the fire switch:
DIP 1 (Conf. firesw.):
On = ALARM condition from 500-3KΩ, (indication of line error by direct
short circuit or open circuit).
Off = ALARM condition from 0-3KΩ (indication of line error by open
circuit).
DIP 2 (Failsafe):
On = Any line error on fire switch or smoke detector puts the control panel
in ALARM condition. This function can be used if cables to fire switches
and smoke detectors are not fireproof.
Off = An error condition does not report ALARM condition.
BVT
1 green LED OK (lights when OK and while closing)
2 yellow LED (lights on error)
3 red LED alarm (emergency opening)
4 ground (-)
5 not used
6 fire switch reset
7 fire switch emergency opening
Jumper J1 must only be set in the last or only fire switch
ON
→
OFF
→
DIP NO
1
2
10
11 12
13
3
4
1
2
7
2,2Ω
10 KΩ
Fire switch BVT No. 1
1
2
3
4
7
2
3
4
7
1
2,2Ω
10 KΩ
Fire switch type BVT
Fit J1 in last
BVT for line monitoring
Ω
Ω
8
Connection of smoke-/heat detectors
Smoke- and heat detectors are connected as shown.
Line monitoring: Correct line monitoring can only be guaranteed with detectors
delivered from the supplier. Other detectors may have different internal resistances
and stand by power consumption.
Comfort ventilation – Connection and settings
The motor output can be controlled separately with a comfort switch.
For comfort ventilation there are the following possibilities:
Potentiometer in Puls pos.:
It is possible to press the »up« button 3 times, which each gives 6 seconds of opening
14
15
time - after that nothing happens – Continuous »up« signal gives 3x6 sec.=18 sec.
- One press on »down« closes the actuator completely for a period which is 18 sec.
longer than the complete opening time - In order to avoid »actuator pumping« max. 3
successive closing attempts will be allowed.
Potentiometer in Const. pos.:
As long as »up« signal or »down« signal are given, the actuators are running
Potentiometer in Puls variable pos.:
The time on the above mentioned pulse opening can be adjusted from 0-60 sec. on the
potentiometre.
When moving the potentiometer into the different positions the LED batt low will
flash for about 4 sec. to indicate when in puls mode. LED line fail flashes 4 sec. when
in constant and AC fail flashes when in puls varaiable.
6
J1
6
6
J1
Actulux A/S
Haandvaerkervej 2
DK 9560 Hadsund
Denmark
DRAWN BY: PSP
TITLE:
ENGELSK
Room thermostats, weekly timers, CCS and
other external control equipment for comfort
ventilation can be connected on the input of the
comfort control.
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Potmeter for
comfort feature
Max.
YEL
YEL
YEL
AC FAIL
LINE FAIL
BATT LOW
Min
18
19
20
Phone int.: +45 98 57 40 90
Fax int.:
+45 96 15 28 00
e-mail: [email protected]
www.actulux.com
DATE: 26-09-17