- ページ 7

ネットワーク・ルーター Cisco N540X-4Z14G2Q-DのPDF インストールの準備をオンラインで閲覧またはダウンロードできます。Cisco N540X-4Z14G2Q-D 14 ページ。
Cisco N540X-4Z14G2Q-D にも: マニュアル (30 ページ)

Cisco N540X-4Z14G2Q-D インストールの準備
Prepare for Installation
• The redundant power option provides a second, identical power supply to ensure uninterrupted power
• Connect each power supply to a separate input power source. Otherwise, it results in a total power failure
• To prevent loss of input power, ensure that the maximum load on each circuit is within the current ratings
• Check the power at your site before installation, and periodically after installation, to ensure that you are
• Provide proper grounding to avoid personal injury and damage to the equipment due to power surges or
Note
Warning
Caution
Note

Site Cabling Guidelines

This section contains guidelines for wiring and cabling at your site. When preparing your site for network
connections to the router, consider the type of cable required for each component, and the cable limitations.
Consider the distance limitations for signaling, ElectroMagnetic Interference (EMI), and connector
compatibility. Possible cable types are fiber, thick or thin coaxial, foil twisted-pair, or unshielded twisted-pair
cabling.
supply.
to the system due to a fault in the external wiring or a tripped circuit breaker.
of the wiring and the breakers.
receiving clean power. If necessary, install a power conditioner.
lightning striking power lines. The chassis ground must be attached to a central office or other interior
ground system.
Cisco N540-6Z18G-SYS-A/D router has single power supply unit.
Statement 1045 Short-Circuit Protection
This product requires short-circuit (overcurrent) protection to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
The router requires external surge protection devices for installations where electrical surges higher than
4KV common mode and 2KV differential mode are expected. Failure to do so can result in permanent
damage to the router. For Cisco N540-6Z18G-SYS-A/D router, 2KV common mode and 1KV differential
modes are supported.
The chassis installation must comply with all the applicable codes, and is approved for use with only
copper conductors. The ground bond-fastening hardware must be compatible and preclude loosening,
deterioration, and electrochemical corrosion of hardware and joined material. Attachment of the chassis
ground to a central office or other interior ground system must be made with a 6-AWG gauge wire
copper ground conductor.