- ページ 8
ネットワーク・ハードウェア Cisco Firepower 4150のPDF マニュアルをオンラインで閲覧またはダウンロードできます。Cisco Firepower 4150 8 ページ。 Rack-mount and ground the chassis
Cisco Firepower 4150 にも: メンテナンスとアップグレードマニュアル (20 ページ), マニュアル (36 ページ), マニュアル (26 ページ), マニュアル (42 ページ), はじめに (42 ページ)
Ground the Chassis
Step 3
Use the crimping tool to secure the grounding cable in the grounding lug.
Step 4
Remove the adhesive label from the grounding pad on the chassis.
Step 5
Place the grounding lug against the grounding pad so that there is solid metal-to-metal contact, and insert the two screws
with washers through the holes in the grounding lug and into the grounding pad.
Figure 6: Attach the Grounding Lug
Step 6
Make sure that the lug and cable do not interfere with other equipment.
Step 7
Prepare the other end of the grounding cable and connect it to an appropriate grounding point in your site to ensure
adequate earth ground.
What to do next
Install the FIPS opacity shield if necessary. See
Install the cables according to your default software configuration as described in the
Getting Started
Rack-Mount and Ground the Chassis
8
Guide.
Install the FIPS Opacity Shield
Rack-Mount and Ground the Chassis
for the procedure.
Cisco Firepower 4100