3. Maintenance
Detectors connected via an Accessory Enclosure should be calibrated and maintained in accordance with
the instructions provided with them. As a minimum Crowcon recommends that detectors are tested every six
months and re-calibrated as necessary.
All alarm output functions from the control panel should be verified on a six-monthly basis, and connections
between the Accessory Enclosure and the detectors and control panel should be check to ensure they are
secure.
4. Specifications
Part Numbers (compatible with Xgard Type 3 and Xsafe mV):
C01919: Single amplifier PCB
C01920: Two amplifier PCB's
C01921: Three amplifier PCB's
C01922: Four amplifier PCB's
Electrical Data
Certification:
Operating voltage:
Current consumption:
Detector input:
Maximum detector cable length: 1km (0.6 miles) using 1.0mm
Output:
Fault signal:
Mechanical Data
Dimensions:
Weight:
Mounting:
Environmental Data
Ingress protection:
Humidity:
Temperature:
Spare Parts an Accessories
Amplifier PCB:
Connector loom
(for fitment to a control panel)
5. Warranty
Warranty Statement
This equipment leaves our works fully tested and calibrated. If within the warranty period of one
year, the equipment is proved to be defective by reason of faulty workmanship or material, we
undertake at our discretion either to repair or replace it free of charge, subject to the conditions
below.
Warranty Procedure
To facilitate efficient processing of any claim, contact our customer support team on 01235 557711
with the following information:
Your contact name, phone number, fax number and email address.
Description and quantity of goods being returned, including any accessories.
Instrument serial number(s).
Reason for return.
www.acornfiresecurity.com
NOT CERTIFIED FOR USE IN A HAZARDOUS AREA
3 wire, 18 - 30Vdc (24V nominal)
50mA per detector
Catalytic Beads 2Vdc (nominal) 300mA
Signal: 10-20mV per % CH4 typical
4~20mA (link selectable as sink or source)
Maximum loop resistance in source mode is 450R
<3mA
220mm (8.6") x 168mm (6.6") x 107mm (4.2")
1.5Kg (3.3lbs) approx.
Four 6mm (1/4") mounting holes at 130mm (5.1") x 180mm (7.1") centres
Indoor use only
0 ~95% RH (non-condensing)
-10 ~ +50ºC (14 to 122º F)
S011753/2
E07632
www.acornfiresecurity.com
2
(17AWG) cable