- ページ 3

アクセサリー Acuity Controls nCM 6 RJB SeriesのPDF 使用方法をオンラインで閲覧またはダウンロードできます。Acuity Controls nCM 6 RJB Series 3 ページ。 Ceiling / surface mount • rear rj-45 port passive infrared (pir) or dual tech (pdt)

A
LEVEL PUSH-BUTTON FUNCTIONS
1
POLE SELECTION / BUTTON MODE
For 2-Pole devices: functions 2 ,5, 6, and 8 can be programmed differently for each pole. The selections
for the Pole Selection function determine which pole's settings are to be modified by subsequent
programming. Button Mode overrides a device and enables its push-button to toggle the device's internal
relay(s) or dim level
3 Copy Pole 1's settings to Pole 2 5 Enable Button Mode
st
1 1
Pole
1
nd
2 2
Pole 4 Disable Button Mode
2
TIME DELAY
The length of time an occupancy sensor will keep the lights on after it last detects occupancy
STANDARD
1 30 sec 3 5.0 min 5 10.0 min
1
2 2.5 min 4 7.5 min 6 12.5 min 8 17.5 min
EXTENDED
1 30 sec 3 30 min 5 60 min 7 90 min 9 120min
2 15 min 4 45 min 6 75 min 8 105 min
3
IDLE TIME UNTIL DIM
The length of time after last detected occupancy that a sensor will reduce lighting to unoccupied dim level.
STANDARD
3 30 sec 3 5.0 min 5 10.0 min 7 15.0 min 9 20.0 min
4 2.5 min 4 7.5 min
1
6 12.5 min 8 17.5 min 10 Disable
EXTENDED
1 30 sec 3 30 min 5 60 min 7 90 min 9 120 min
2 15 min 4 45 min 6 75 min 8 105 min 10 Disable
3
START TO HIGH
Lights go to full bright for 20 minutes upon initial power up
5 Disabled
1
2 Enabled
4
AUTO SET-POINT / 100 HOUR BURN-IN
100 HOUR BURN-IN: Overrides relays on (typically for lamp seasoning)
AUTO SET-POINT: Photocell calibration procedure for detecting optimum lighting control level
1 Disabled
1
3 Enabled then run Auto-Setpoint 5 Blink back Set-Point
2 Enabled 4 Run Auto Set-Point
1
2
DEFAULT SETTING
REQUIRES PRESS & HOLD METHOD
TEN'S DIGIT OF SET-POINT
5
The ten's digit of the target light level that is to be maintained by the device (in foot-candles)
1 10 fc
3 30 fc
5 50 fc
2 20 fc
4 40 fc
6 100 fc
ONE'S DIGIT OF SET-POINT
6
The one's digit of the target light level that is to be maintained by the device (in foot-candles)
1 1 fc
3 3 fc
5 5 fc
2 2 fc
4 4 fc
6 6 fc
7
SUNLIGHT DISCOUNT FACTOR
Value used to improve the tracking accuracy of a photocell during periods of high daylight. Decreasing the
value will lower the controlled level of the lights
1 x/1
1
3 x/3
5 x/5
2 x/2
4 x/4
6 x/6
8
INCREMENTAL SET-POINT ADJUSTMENT
Alters the target light level that is to be maintained by the device (in foot-candles)
1 Decrease 1 fc
2 Increase 1 fc
9
RESTORE FACTORY DEFAULTS
1 Maintain Current
2 Restore Defaults
10
TIME DELAY SCHEME
2
Selects the range of time delay values available for use by function 2, Time Delay.
POLE 1
POLE 2
1 Standard
Standard
3 Extended
2 Standard
Extended
4 Extended
11
PHOTOCELL MODE
2
Indicates a photocell sensors method of operation. One mode enables the sensor to turn the lights both
on and off while the other mode can only inhibit (prevent) the lights from turning on
1 Full On/Off Control
1
2 Inhibit Only Control
11
DUAL ZONE PHOTOCELL MODE
Indicates a Dual Zone photocell sensor's method of operation
STEPPED DIMMING (DUO) MODE :
Mode where the appropriate on/off combination of
the two associated relays is maintained in order to
always meet the photocell set-point requirements
STEPPED DIMMING (DUO) MODE –
NEVER OFF:
Mode where the appropriate on/off combination
of the two associated relays (except both off) is
maintained in order to always meet the photocell
set-point requirements.
1 Duo
1
2 Duo-Never Off
Acuity Controls | 900 Northrop Road, Wallingford, CT 06492 PHONE: (800)-727-7483 nLightcontrols.com ©2015 Acuity Brands Lighting, Inc. All rights reserved. 10/26/20
2
7 15.0 min 9 20.0 min
7 200 fc
10 0 fc
1
8 Disable
1
7 7 fc
9
9 fc
8 8 fc
10 0 fc
7 x/7
9 x/9
8 x/8
10x/10
2
POLE 1
POLE 2
Standard
Extended
2
(DZ Models Only)
DUAL ZONE OFFSET MODE : Mode where Zone
2's set-point is a selected percentage higher than
Zones 1's set-point
DUAL ZONE FAN MODE : Mode where Zone 2's
photocell control is disabled
3 Offset
4 Fan Mode
12
DUAL TECHNOLOGY (MICROPHONICS
A second method of occupancy detection that allows the sensor to hear occupants
1 Normal
1
13
MICROPHONE GRACE PERIOD TIME
The time period after lights are automatically turned off that they can be voice reactivated
1 0
2 10
1
15
PHOTOCELL DIMMING RANGE (HIGH)
The maximum output level (0-10 VDC) up to which an automatic dimming photocell will control
1 Off
2 1 Volt
16
PHOTOCELL DIMMING RANGE (LOW)
The minimum output level (0-10 VDC) down to which an automatic dimming photocell will control
1 Off
1
2 1 Volt
17
DUAL ZONE OFFSET
Fixed voltage increase of Zone 2's dimming output from Zone 1's dimming output (Dual Zone photocell
applications only)
1 -10 Volts 5 -6 Volts 9 -2 Volts 13 2 Volts
2 -9 Volts 6 -5 Volts 10 -1 Volt
3 -8 Volts 7 -4 Volts 11 0 Volts 15 4 Volts 19 8Volts
4 -7 Volts 8 -3 Volts 12 1 Volt
18
DUAL ZONE OFF POINT
Zone 2's set-point as a percentage of Zones 1's set-point (Dual Zone photocell applications only)
1 110%
2 120%
19
DIMMING RATE
The speed at which automatic changes to the light level occur
1 700 sec 2 350 sec 3 70 sec
20
LED
2
Indicates the behavior of a device's LED
3
7 Normal
1
2 Inhibited
21
PHOTOCELL TRANSITION OFF TIME
The time period for which a photocell must measure a light level above the set-point before it will turn the
lights off
1 45 sec
2 2 min
22
PHOTOCELL TRANSITION ON TIME
The time period for which a photocell must measure a light level below the set-point before it will initiate the
lights on
1 45 sec
1
2 2 min
23
OCCUPIED BRIGHT LEVEL
The output level (0-10 VDC) that a dimming sensor sets the light to when occupancy is detected (not
applicable if photocell is enabled)
1 1 Volt
2 2 Volts
24
UNOCCUPIED DIM LEVEL
The output level (0-10 VDC) a dimming sensor sets the lights after the idle time until dim timer expires
1 1 Volt
1
2 2 Volts
26
FOLLOW PHOTOCELL MODE
Instructs how a device's dimming output reacts relative to a dimming photocell
1 Disabled
2 Enabled Negative Only
27
SWEEP EXIT TIME
The time period before a sweep is executed
1 0 sec
2 15 sec
1
28
SWEEP GRACE PERIOD
The remaining time delay after a sweep is executed
1 0 sec
2 5 sec
1
1
DEFAULT SETTING
3
The LED will blink back the ten's digit, then pause, then blink back the one's digit. For a "0" the LED will blink
very rapidly. The sequence is repeated 3 times.
5 Inhibit
FAMILY INSTRUCTIONS
2 Off
3 Medium 4 Low
2
3 20
5 40
7 60
4 30
6 50
3 2 Volts
5 4 Volts
7 6 Volts
4 3 Volts
6 5 Volts
8 7 Volts
3 2 Volts
5 4 Volts
7 6 Volts
4 3 Volts
6 5 Volts
8 7 Volts
14 3 Volts 18 7 Volts
16 4 Volts 20 9 Volts
2
3 130%
5 150%
1
7 170%
4 140%
6 160%
8 180%
1
4 35 sec
3 5 min
1
5 15 min 7 25 min
3
4 10 min
6 20 min
2
3 5 min
5 15 min 7 25 min
4 10 min
6 20 min
3 3 Volts
5 5 Volts
7 7 Volts
4 4 Volts
6 6 Volts
8 8 Volts
3 3 Volts
5 5 Volts
7 7 Volts
4 4 Volts
6 6 Volts
8 8 Volts
1
3 Enabled Both Positive and Negative
3 30 sec
5 1 min
7 3 min
4 45 sec
6 2 min
8 4 min
3 10 sec
5 30 sec
4 15 sec
6 1 min
2
REQUIRES PRESS & HOLD METHOD
nCM xx RJB
TM
)
9 8 Volts
1110 Volts
1
109 Volts
9 8 Volts
1110 Volts
10 9 Volts
1
17 6 Volts
21 10 Volts
9 190%
10 200%
5 7
sec
9 9 Volts
10 10 Volts
1
9 9 Volts
10 10 Volts
9 5 min
2 of 2