- ページ 5
コントローラー Acuity Controls ECLYPSE A1000のPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。Acuity Controls ECLYPSE A1000 10 ページ。 Asset tracking
Acuity Controls ECLYPSE A1000 にも: インストレーション・マニュアル (14 ページ)
2.0 - Mounting Instructions
2.1 Mounting Positions
The controller's mounting orientation must be horizontal
with the controller's back attached to a verical wall
surface.
Figure 5: Permitted Mounting Positions - Vertical Mounting is Forbidden
Horizontal Mounting Position:
Required for DIN rail mounting
Required for wall mounting
2.2 Assembly Order
Modules are connected in a left to right order, starting
with a PS24 Power Supply then the ECLYPSE A1000AT
server module.
2.3 DIN Rail-Mounted Installation
1. Securely mount the DIN rail horizontally on the wall.
2. Clip the modules onto the DIN rail in the assembly
order.
3. Slide the modules together so that the side connec-
tors of each module are firmly mated with the adjoin-
ing module. Use DIN rail clips to keep the row of
modules well secured together and to prevent the
movement of any module along the DIN rail. Certain
modules come with DIN rail clips in the box.
4. To detach the module from the DIN rail, separate the
module from any other module located on either side.
Use a flat screw driver to pull down on the release clip
located at the bottom center of the module and pull it
off the DIN rail, bottom first.
Figure 6: DIN Rail Release Clip
2.4 Wall Mounted Installation
Modules should be mounted on a wall one module at a
time. The first module of the assembly to be mounted
should be the one to the very left (usually a PS24 Power
Supply). Once this module has been attached to the wall,
connect the next module on the right so that the side
connectors are firmly coupled and the modules are
aligned straight. Now attach this module to the wall.
Repeat until all modules are mounted in a row.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017-2019 Acuity Brands Lighting, Inc. All rights reserved. 03/29/19
Vertical Mounting Position:
Is Forbidden
1. Before mounting a module, separate the front
assembly from the back plate of each module to be
mounted: push the two latches up to unlock a
module's front assembly as shown below.
•
For server and power supply: Separate the front
and back base by gently pulling the front assembly
off of the back base, thereby separating the electri-
cal connectors between the two halves.
Figure 7: Latches to Unlock a Module's Front Assembly
2. Once the front assembly has been removed, use the
back plate's mounting holes to mark the location of
any holes that need to be drilled.
Figure 8: Typical Mounting Holes
3. Drill the holes.
4. Clean the surface and mount the module using a No.
8 slotted hex, size: 1/4" or equivalent mounting hard-
ware appropriate to the wall.
Figure 9: Appropriate Mounting Hardware (field supplied)
5. To lock a module's front assembly in place, attach the
front assembly to the module's back base by closing
any gull-wing front assemblies (if applicable) and
pushing the two latches down.
A1000AT_IG_10_EN
5 of 10