WSX D INSTRUCTION SHEET

OPERATIONAL SETTINGS

2 = Occupancy Time Delay
The length of time an occupancy sensor will keep the lights on after it last detects occupancy.
1 - Test Mode**
5 - 7.5 min
9 - 17.5 min
2 - 30 sec
6 - 10.0 min*
10 - 20.0 min
3 - 2.5 min
7 - 12.5 min
11 - 22.5 min
4 - 5.0 min
8 - 15.0 min
12 - 25.0 min
**Test mode sets Occupancy Time Delay to 30 seconds, and increases photocell transition rate
in addition to disabling the microphone on units with Dual Technology.
3 = On Mode
Automatic On
Sensor automatically turns the lights on when it detects occupancy.
Manual On
Sensor requires pressing the button to turn the lights on.
Reduced Turn-On
Sensor is set to initially only detect large motions, effectively ignoring any reflected Passive
Infrared (PIR) signals. Occupants will still be detected immediately when they enter the room as
their PIR signal is large. Once lights are on, the sensor returns to maximum sensitivity.
1 - Automatic On*
3 - Reduced Turn-On
2 - Manual On

4 = Switch Modes

Switch Enable (Override Off)
Button will turn lights off and keep them off until pressed again. The lights will remain off until
the button is pressed again, restoring the sensor to Automatic On mode.
Switch Disable
User is prevented from turning off the lights via the push-button.
Predictive Mode
Pressing the push-button switch overrides the lights off and temporarily disables the occupancy
detection. After 10 seconds, the occupancy detection reactivates and monitors for an additional
30 seconds. If no occupancy is detected during this period, the sensor will revert to Automatic On
operation. If occupancy is detected, the sensor will remain in Override Off mode and requires the
switch to be pressed again in order to restore the sensor to Automatic On.
Predictive Mode with Expiration
Pressing the push-button switch overrides the lights off and temporarily disables the occupancy
detection. After 10 seconds, the occupancy detection reactivates and monitors for an additional
30 seconds. If no occupancy is detected during this period, the sensor will revert to Automatic
On operation.
1 - Switch Enable
3 - Predictive Mode
2 - Switch Disable
4 - Predictive Mode with Expiration*

5 = Darkness Set-Point / Inhibit Set-Point

The ambient light level at which the sensor sets the lights to the High Trim setting.
1 - Set Now**
5 - 8 fc
9 - 48 fc
2 - 0.1 fc
6 - 16 fc
10 - 64 fc
3 - 1 fc
7 - 24 fc*
11 - 80 fc
4 - 4 fc
8 - 32 fc
12 - 96 fc
**Set Now will automatically select the Darkness Set-Point based on the current conditions
in the room. Lights will go to full bright and sensor will rapid flash for 15 seconds allowing
occupant to move out of direct view of sensor. Once the set-point selection is completed, the
sensor will double-blink in confirmation.
RENUNCIA:
Este documento ha sido traducido del inglés por razones de conveniencia.
En el caso de cualquier inconsistencia entre el texto del documento en
inglés y esta traducción, el texto en inglés controla.
Todas las marcas registradas a las que se hace referencia son propiedad
de sus respectivos dueños. Marcas comerciales de Acuity Brands Las luces
que están marcadas con el símbolo ® están registradas en los EE. UU. Y
pueden estar registradas en otros países.
5-year limited warranty. Full warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Specifications subject to change without notice.
Actual performance may differ as a result of end-user environment and application.
www.acuitycontrols.com
6 = Daylight Set-Point
The ambient light level at which the sensor sets the lights to the Low Trim setting.
13 - 27.5 min
1 - Set Now**
14 - 30.0 min
2 - 0.1 fc
3 - 1 fc
4 - 4 fc
**Set Now will automatically select the Daylight Set-Point based on the current conditions
in the room. Lights will go to full dim and sensor will rapid flash for 15 seconds allowing
occupant to move out of direct view of sensor. Once the set-point selection is completed, the
sensor will double-blink in confirmation.
7 = Photocell Mode
Inhibit Only
Prevents lights from automatically coming on when light level is above the Inhibit Set-Point
Adaptive Daylight Harvesting
Dims lights from high trim to low trim setting according to Darkness and Daylight set-points.
1 - Disabled*
2 - Inhibit Only
8 = Dim to Off Occupancy Time Delay
After the Occupancy Time Delay (Function 2) has expired, this setting specifies the amount of
time lights are held at Low Trim (Function 16) before turning off.
1 - 0 sec*
2 - 30 sec
3 - 2.5 min
4 - 5 min
9 = Restore Defaults
Returns all functions to original settings.
1 - Maintain Current*
2 - Restore Defaults
10 = Minimum On Time
Required initial time for lamps to be on after each switch on, regardless of occupancy status.
Once met, lights resume following occupancy time delay.
1 - 0 min (disabled)*
2 - 15 min
3 - 30 min
11 = LED Operation
13 - 128 fc
Indicates behavior of device's LED.
14- 192 fc
1 - Occupancy Indication*
15 - 256 fc
2 - Disabled
12 = Dual Technology (Microphonics™)
The secondary method of occupancy detection that allows the sensor to hear occupants.
1 - Normal*
2 - Off
3 - Medium
800-535-2465
5 - 8 fc
9 - 48 fc
13 - 128 fc
6 - 16 fc
10 - 64 fc*
14- 192 fc
7 - 24 fc
11 - 80 fc
15 - 256 fc
8 - 32 fc
12 - 96 fc
3 - Adaptive Daylight Harvesting
5 - 7.5 min
9 - 17.5 min
6 - 10 min
10 - 20 min
7 - 12.5 min
11 - Stays at dim (never off)
8 - 15 min
4 - 45 min
5 - 60 min
4 - Low
5 - Phase Off (15-10-5 min)
911-00059-003

13 = Microphone Grace Period

Time period after lights are automatically turned off that they can be voice reactivated.
1 - 0 sec
5 - 40 sec
2 - 10 sec*
6 - 50 sec
3 - 20 sec
7 - 60 sec
4 - 30 sec
14 = Manual On Grace Period
Time period after lights automatically turn off that they can be reactivated by motion. Applicable
only when sensor is in Manual On (Semi Auto) mode.
1 - 0 sec
3 - 15 sec*
15 = Dimming Range Max (High Trim)
The maximum output level of the sensor.
1 - 0 VDC
5 - 3 VDC
9 - 7 VDC
2 - 1 VDC
6 - 4 VDC
10 - 8 VDC
3 - 1.5 VDC
7 - 5 VDC
11 - 9 VDC
4 - 2 VDC
8 - 6 VDC
12 - 9.1 VDC**
**Default for EZ option
16 = Dimming Range Min (Low Trim)
The minimum output level of the sensor.
1 - 0 VDC
5 - 3 VDC
9 - 7 VDC
2 - 1 VDC*
6 - 4 VDC
10 - 8 VDC
3 - 1.5 VDC**
7 - 5 VDC
11 - 9 VDC
4 - 2 VDC
8 - 6 VDC
12 - 9.1 VDC
**Default for EZ option
17 = Predictive Exit Time
Time period after manually switching lights off for occupant to leave the space. Applicable only
when sensor is in Predictive Off mode.
1 - 5 sec
4 - 8 sec
7 - 15 sec
2 - 6 sec
5 - 9 sec
8 - 20 sec
3 - 7 sec
6 - 10 sec*
9 - 30 sec
18 = Predictive Grace Time
Time period after Predictive Exit Time that sensor rescans the room for remaining occupants.
Applicable only when sensor is in Predictive Off mode.
1 - 0 sec
4 - 20 sec
7 - 50 sec
2 - 5 sec
5 - 30 sec*
8 - 60 sec
3 - 10 sec
6 - 40 sec
19 = Fade On Rate
Time required for light to reach preset level.
1 - 0.75 sec*
3 - 5 sec
2 - 2.5 sec
4 - 15 sec
20 = Fade Off Rate
Time required for light to turn Off.
1 - 0.75 sec
3 - 5 sec
2 - 2.5 sec*
4 - 15 sec
21 = Start Level
Level of light output when occupancy is initially detected. Not applicable in Automatic Dimming
Control (ADH) mode.
1 - 10%
4 - 40%
7 - 70%
10 - 100%*
2 - 20%
5 - 50%
8 - 80%
3 - 30%
6 - 60%
9 - 90%
PAGE 3
13 - 10 VDC*
13 - 10 VDC
* DEFAULT SETTING