- ページ 7

エアコン Toshiba 24S SeriesのPDF インストレーション・マニュアルをオンラインで閲覧またはダウンロードできます。Toshiba 24S Series 10 ページ。 Air conditioner (split type)

NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the
connecting pipes to the auxiliary pipes and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape
tightly. In case of leftward piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not stick out of the rear
plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to one
another and cut off the insulating tape wound on the connecting pipe to
avoid double-taping at the joint; moreover, seal the joint with the vinyl
tape, etc.
Since dewing results in a machine trouble, make sure to insulate both
connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it, not to crush it.

Indoor Unit Fixing

1. Pass the pipe through the hole in the wall and hook the indoor unit on the
installation plate at the upper hook.
. Swing the indoor unit to right and left to confi rm that it is fi rmly hooked up
on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on
the installation plate. Pull the indoor unit toward you to confi rm that it is
fi rmly hooked up on the installation plate.
Hook here.
1
1
Installation plate
2
Hook
For detaching the indoor unit from the
installation plate, pull the indoor unit
toward you while pushing its bottom
up at the specifi ed parts.

Installation Place

A place which provides enough spaces around the outdoor unit as shown
in the diagram.
A place which can bear the weight of the outdoor unit and does not allow
an increase in noise level and vibration.
A place where the operation noise and discharged air do not disturb your
neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not block a passage.
When the outdoor unit is to be installed in an elevated position, be sure to
secure its feet.
An allowable length of the connecting pipe is up to 0 m (18 class) or 5 m
(4 class).
An allowable height level is up to 8 m (18 class) or 10 m (4 class).
A place where the drain water does not cause any problems.
Precautions about Installation in Regions
with Snowfall and Cold Temperatures
Do not use the supplied drain nipple for draining water. Drain the water from
all the drain holes directly.
To protect the outdoor unit from snow accumulation, install a holding frame,
and attach a snow protection hood and plate.
* Do not use a double-stacked design.
Indoor unit
Connecting cable
Press
(unhook)
Push
Push

OUTDOOR UNIT

5
Information
The lower part of indoor unit may fl oat,
due to the condition of piping and you
cannot fi x it to the installation plate. In
that case, use the % screws provided
to fi x the unit and the installation plate.

Drainage

1. Run the drain hose sloped downwards.
NOTE
The hole should be made at a slight downward slant on the outdoor side.
Do not rise the
drain hose.
50 mm
or more
Do not put the drain hose
end into water.
. Put water in the drain pan and make sure that the water is drained out of
doors.
3. When connecting extension drain hose, insulate the connecting part of
extension drain hose with shield pipe.
Shield pipe
Inside the room
Drain hose
CAUTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and
other parts at a height above the drain guide.
Snow protection plate
Snow protection hood
Front
At least 50 cm
Snow accumulation line
Anchor bolts
Holding frame
CAUTION
1. Install the outdoor unit in a location where there are no obstructions
near its air intake or air outlet.
. When the outdoor unit is installed in a place that is always exposed to
strong winds like on the coast or on a high story of a building, secure
the normal fan operation using a duct or a wind shield.
3. Especially in windy areas, install the unit to prevent the admission of
wind.
4. Installation in the following places may result in trouble.
Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfi de gas.
A place where high-frequency
waves are likely to be generated,
such as from audio equipment,
welders, and medical equipment.
Toshiba 1110651160 (EN)
%
%
Screw
Screw
Do not form the drain hose
into a wavy shape.
Do not put the drain hose
end in the drainage ditch.
Extension drain hose
Wall
Drain
guide
Space for pipes
Install at least 50 cm
above the snow
accumulation line.
Strong
wind