<In case of connecting one group operation of
indoor units and two indoor units>
Single port type FS unit
Piping
Control wiring between
Remote
indoor unit and FS unit
control
(Within 49 ft (15 m))
Group control
[ 0E ] :
1
1
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
Multi port type FS unit
Piping
Remote
control
Group control
[ 0E ] :
1
1
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
<In case of connecting four indoor units>
Single port type FS unit
Piping
Control wiring between
indoor unit and FS unit
(Within 49 ft (15 m))
Remote control
[ 0E ] :
0
0
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
Multi port type FS unit
Piping
Remote control
[ 0E ] :
0
0
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
53-EN
<Incorrect connection examples>
Incorrect
Single port type FS unit
Single port type
FS unit
Piping
Indoor unit
Control wiring
Remote control
between indoor
unit and FS unit
0
(Within 49 ft (15 m))
1
Group control
0
Incorrect
Multi port type FS unit
Piping
Indoor unit
Remote control
Group control
0
Incorrect
1
0
Multi port type FS unit
Piping
Indoor
unit
Indoor unit
Remote control
0
Group control
1
0
Incorrect
Multi port type FS unit
Piping
Indoor
unit
Indoor unit
Remote control
Group control
0
1
0
– 27 –
10

Test run

CAUTION
• Turn on the power and turn on the case heater of
the compressor.
To save the compressor when it is activated, leave
Indoor unit
the power on for more than 12 hours.
■ Methods of test run
Single port type FS unit
◆ A test run is executed by using a
remote control
Operate the system normally to check the running
condition using the wired remote control. Follow the
instructions in the supplied owner's manual when
operating the unit.
Indoor
unit
If a wireless remote control is used for operations,
follow the instructions in the installation manual
supplied with the indoor unit.
To execute a test run forcibly under the condition that
the thermostat automatically turns the unit off due to
the indoor temperature, follow the procedure below.
The forcible test run will automatically stop after 60
minutes to prevent continuous forcible running and
Multi port type FS unit
return to normal running.
CAUTION
Do not use forcible running except for a test run as it
overloads the unit.
TEMP.
FILTER
RESET TEST
1, 5
1
Push and hold the
4 seconds. TEST appears on the LCD and
the unit enters the TEST mode.
2
3
NOTE
• Do not run the unit in any mode other than COOL or
HEAT.
• The temperature setting cannot be changed during
the test run.
• Check codes are detected as usual.
4
5
2, 4
ON / OFF
3
TIMER SET
TIME
SET CL
TEST
button for more than
TEST
ON / OFF
Push the
button.
Push the
MODE
button to switch the running
mode to COOL or HEAT.
TEST
ON / OFF
Push the
button to stop running
after fi nishing the trial run.
The indication on the LCD display returns
to the status of procedure 1.
TEST
Push the
button to exit the test mode.
(TEST disappears on the LCD display and
the status changes to normal stopped
mode.)
54-EN