Dimplex ARC10A ユーザーマニュアル
Architectural Air Curtains
Models : ARC10E, ARC15E, ARC20E, ARC10W, ARC15W, ARC20W, ARC10A, ARC15A & ARC20A
IMPORTANT: THESE INSTRUCTIONS SHOULD BE READ CAREFULLY AND RETAINED FOR FUTURE REFERENCE

IMPORTANT SAFETY ADVICE

DO NOT COVER OR OBSTRUCT the air inlet or outlet grille.
ENSURE THE APPLIANCE IS EARTHED.
Do not use this heater in areas where excessive dust exists.
Do not use this heater with young children unattended.
This appliance is not intended for use by children or other
persons without assistance or supervision if their physical,
sensory or mental capabilities prevent them from using it
safely. Children should be supervised to ensure that they
do not play with the appliance.
The heater carries the Warning symbol indicating that
it must not be covered.
Warning: In order to avoid overheating, do not cover the
heater.
This heater must not be located immediately above or below
a fixed socket outlet or connection box.
Always disconnect supply before working on the product.
This appliance should only be connected to the fixed wiring
of the premises by means of conduit.
This product should be mounted safely to solid wall, floor
or ceiling surfaces only.
If mounting the appliance horizontally it should not be
mounted less than 1.8m from the floor.
This product must not be subjected to water spray or
immersion.
Ensure the supply cables are of adequate current carrying
capacity and are protected by a suitable fuse.
This appliance should not be mounted in a toilet or
washroom.
Ensure proper manual handling procedures are observed
at all times.
WARNING: Isolate electrical supply to ALL modular linked
units when carrying out maintenance.
Models
Model
Heat
Electrical
output
kW
AMBIENT
ARC10A
220-240V ~1PN
n/a
ARC15A
220-240V ~1PN
n/a
ARC20A
220-240V ~1PN
n/a
ELECTRICALLY HEATED
ARC10E
6.0 / 12.0
380-415V ~3PN
ARC15E
9.0 / 18.0
380-415V ~3PN
ARC20E
12.0 / 24.0
380-415V ~3PN
WATER HEATED (at 82/71 °C - LPHW)**
ARC10W
12
220-240V ~1PN
ARC15W
18
220-240V ~1PN
ARC20W
24
220-240V ~1PN
Electrical
The installation of this appliance should be carried out by a
competent electrician and be in accordance with the current IEE
wiring regulations.
Weight
Electrical
Supply
load
(per phase)
kg
A
1.5
55
2.3
82.5
3.0
110
18
60
27
90
36
120
1.5
65
2.3
95
3
130
Fixing Positions
This appliance may be either fixed to a ceiling - see Fig. 1 or floor
mounted see Fig. 2 using an appropriate foot.
A minimum distance of 500mm is required from top of the
appliance to the ceiling (see Fig. 1) and also the distance between
the bottom of the appliance and the top of the door should be
kept to a minimum (see 'C' in Fig. 1).
To open the appliance, remove the inlet grilles ('x' in Fig. 3)
Remove the front panel ('z' in Fig. 3).
Horizontal Mounting
By using the fixing holes in the top of the air curtain, attachment
to a ceiling over the product can be achieved using suitable M10
threaded steel rod or similar supports of sufficient strength -
see 's' in Fig. 1.
Vertical Mounting
The architectural range of air curtains can be vertically mounted
using a suitable floor foot (Ref: ARCVMF). Contact Dimplex or
your service agent for further information. Refer to Fig. 2 for fixing
details.
Electrical connection
All products are fitted with a microprocessor control. Electrical
power and control connections are made as shown in Fig. 6 & 7.
A suitable local isolating switch must be provided in the electrical
supply circuit with at least 3mm clearance on each pole. In
order to access the electrical connections, remove the inlet grilles
(see 'x' in Fig. 3). Remove the front panel (see 'z' in Fig. 3) and
also remove the mains cover plate (see 'y' in Fig. 3).
ARC Electric Models
Feed an appropriate supply cable as shown in Fig. 4 and attach
to the terminal block (see 'a' in Fig. 4).
Note: Ensure that cables are secured to the cable tray with fixing
ties to avoid contact with the elements.
ARC Water/Ambient Models
Feed an appropriate supply cable as shown in Fig. 5 and attach
to the terminal block (see 'a' in Fig. 5).
A suitable cable for a switch panel (kit ref. - CABC1 for electrically
heated models or CABC2 for water heated/ambient models)
Recom-
can be similarly introduced through the top panel and connected
mended
height
to the circuit board.
If the unit is to be operated in conjunction with a door switch, a
m
normally closed switch should be wired (see 'D' in Fig. 6 & 7) as
appropriate - see also 'Switch Panel Instructions'.
3.75
If the unit is to be connected to a Building Energy Management
3.75
System, connections to be made (see 'G' in Fig. 6 & 7) as
3.75
appropriate.
Ensure that the air curtain is securely fastened in position and
3.75
that the supply cables are firmly clamped before operating the
3.75
appliance.
3.75
Water connection
3.75
Models designed for use in conjunction with a low pressure hot
3.75
water supply should be individually connected (in a parallel
3.75
circuit) to the flow and return pipe-work.
Connections (see 'a' in Fig. 8) are ¾" BSPT and isolation valves
(see 'b' in Fig. 8) should be fitted as close to the air curtain
connection points as possible. Care should be taken to release
as much air as possible to prevent air locks.
Maximum water supply conditions are 100ºC and 10 bar
(1.03MPa).