Mounting and removal

Wiring

Conductor cross-section of 1.5 mm² must not be undercut.
Use Copper wires approved up to 60°C/75°C.
For of wire end sleeve is recommended.
Loads connected to the measuring wires are not allowed.
The placing of the measuring wires has to avoid a cross connection or short. Laying in cable channel.
The regulations according to EN 60204-1 are to be followed.
Use effective protective circuits parallel to an inductive load to avoid a shortcut of the output contacts.
The arrangements of the overcurrent protective mechanism are to consider.
Overvoltage > 32V DC destroys the unit.
Use power supply with max. 32V output voltage also with fault..

Commissioning

Switch off the unit befor you start working.
Wire the unit according to intended use
Connect the power supply 24V DC to A1 and 0V to A2.
Self-test follows. After faultless self-test the unit is in function. The LED OK is green

Example of application

Application: Output contacts connected in parallel
L1
L2
L3
≤ 3A
FU/ FC
14
Test?
24
≤ 3A
∑6A
U1 V 1 W1
M
3
U2
V1
U1
V2
W1
W2
12
24V
A1
Q
13
b8
SET
L1
b4
L2
DN3PD1
b2
L3
b1
A2
O1
O2
14
NC
14
Application: Output contacts connected in series
L1
L2
L3
≤ 3A
23
FU/ FC
23
U1 V 1 W1
24
24
3
U1
W2
24V
Test?
A1
Q
b8
SET
L1
b4
L2
DN3PD1
b2
L3
b1
M
A2
O1
O2
U2
V1
NC
V2
W1