Connecting a flexible jointless stainless steel pipe to a
threaded attachment
GB
Suitable for connection with a flexible hose assembly. The flexible hose
assembly must be certified to AS/NZS 1869 class B or D, be of
appropriate internal diameter for the total gas consumption, be kept as
short as possible (not exceeding 1200mm), must not be in contact with
the floor or any hot or sharp surfaces. The hose assembly must not be
subject to strain, abrasion, kinking or deformation.
E ns u r e pipe s do not touch any moving parts and
is not compressed.
! Only use pipes and seals that comply with current
national regulations.
Burner and nozzle specifications
Table 1
Burner
Fast (R)
Semi Fast (S)
Auxiliary (A)
Test point pressure
P lace the supplied duplicate data plate to a suitable adjacent surface or within the instruction manual for future reference.
14
Burner
Gas Consumption Injector
(mm)
(MJ/h)
Nomin al
157
7 . 5
132
5.0
110
2.5
1.0 kPa with both Semi Fast
burners operating at high
S
A
Checking the tightness of the connection
! When the installation process is complete, check the
pipe fittings for leaks using a soapy solution. Never use a
flame.
Operation of the appliance must be tested by the installer before leaving.
Check all burner flames are blue in colour, stable and completely ignite
at both high and low flame settings with no appreciable yellow tipping,
carbon deposition, lifting, floating, lighting back or objectionable odour.
Test burners individually and in combination.
For other minor adjustments or if the appliance does not
perfrom correctly; contact Arisit Pty Ltd 1300 762 219
Natural Gas
Adjusting the burner's
(1.0 kPa)
(Primary air)
(mm)
125
100
72
S
R
A
(mm)
4.7
2.6
2 .0