Blower
The external blower pushes air through blower duct to the fireplace, where it is heated and distributed into the
room. The blower may be located to draw air from the exterior of the home, producing positive pressure inside
the home and providing outside air for the combustion chamber. Or, if desired, the blower may be located to draw
air from the interior of the home.
Exterior
Fireplace
Interior of Home
•
Do not draw air from confined areas or from a
garage or area containing fumes or emissions.
The blower inlet must be a minimum 36" below
any exhaust vent.
•
The blower may be installed to draw air from a
crawl space or attic if approved by local building
codes. NOTE: certain codes require a fire
curtain in these cases.
•
The shorter the blower duct, the greater the air
flow.
•
A maximum of two 90° bends may be used.
•
The maximum length for 6" diameter blower duct is 15' (use the included duct & start collar)
•
The maximum length for 8" diameter blower duct is 25' (use two 6" to 8" adapters)
•
Connect the blower duct to the
right, left, or bottom of the fireplace.
Each location is sealed with a
cover plate (use a 5/16" nutdriver
to remove cover plate). If using the
bottom location, remove the 8-1/2"
by 6-1/4" air deflector directly
above the cover plate and attach
the duct to the 6" hole above the
deflector. Insert the starter section
into the blower hook-up hole and
bend the flanges outwards, locking
the starter section in place.
•
Attach the flex duct to the collar on
the blower box and start collar
using duct tape and/or screws
•
The blower, if located on an external wall, must be weatherproofed. Apply caulk around the perimeter of the
blower housing where it contacts the external wall and vapor barrier (apply sparingly).
Part # 17601185
44E - ZC Builder Booklet
TM
Internal Blower
Exterior Wall
© 2002, Travis Industries, Inc.
Exterior
Exterior Wall
TOP
Ring for
duct
VIEW
11-3/8"
6"
Hole for
Conduit
1-1/2"
Conduit Cover Plate
(On both sides)
Fireplace
Xtrordinair
6" Blower
Hook-Up
External Blower
Fireplace
Interior of Home
The blower may be placed
in a ventilated crawl space
(if approved by the local
building department).
NOTE: The blower may be
placed with the grill facing
down. Do not place the
blower on its side.
Height: 13"
FRAMING
Width: 11-3/8"
DIMENSIONS:
Depth: 11-1/2"
Snap conduit
connector into the
hole in the top of
the blower housing.
Wire
Plugs
Locking Tabs
Start Collar
Blower
Housing
Flex Duct
Min. 4"
11 1/2"
Page 7
13"
Intake grill
must be
accessible.
Power Source
(120 Volt A.C.)
Printed 3/8/02