Fire Detection and Activation System
Model 08451
Rev 3.1

Vehicle and Mobile Plant Installation Notes (AS5062)

15
For AS5062 vehicle installations, a risk assessment must be completed all equipment, and the
design agreed upon by the installer and operators.
The risk assessment should include
identification of all fuel and ignition sources, and these must be considered in the system
design.
AS 5062 requires:
Automatic Discharge: The system shall be programmed for automatic discharge on alarm
unless it is determined by the risk assessment why automatic discharge would be inappropriate.
Equipment Shutdown:
As determined by the risk assessment, any equipment that may
impede operation of the fire system must be shutdown prior to system discharge. This requires
the installation of the FP-08860 Shutdown Relay Module.
Secondary Power Supply: In addition to the power supply requirements as per 3.1 Power
Supply Input, AS5062 also requires a secondary power supply capable of operating the fire
system for a minimum of 24 hours. This requires the installation of the Power Control Module,
or the identification of a secondary power source in the equipment that will not be affected by
any failure of the primary power supply.
System Discharge Advice:
AS5062 requires independent notification of the suppression
system discharged. This requires the installation of the FP-08825 Thermal Fuse Coupling.
Manual Actuation: Should manual actuators must be installed on Circuit 1 Alarm to allow for
remote manual activation of the suppression system. This requires the installation of FP-14053
Manual Actuators and Circuit 1 Alarm to be programmed for automatic discharge.