- ページ 6
コントロールパネル FirePro Sigma XTのPDF 設置および操作マニュアルをオンラインで閲覧またはダウンロードできます。FirePro Sigma XT 14 ページ。 Conventional fire control panel with control unit for aerosol release, system isolation
FirePro Sigma XT にも: 手続き (4 ページ)
3.1.2.
Connecting more than 3 Signs
For systems requiring more than 3 signs (or devices), wiring is as follows:
Notes: •
FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS.
•
Connections for the first 3 signs or devices remains the same as the previous wiring diagram.
•
For more than 3 signs, a separate power supply is required from the 24VDC output on the FIP.
•
STATUS SERIAL (RS485) - Maximum number of devices, including both Signs and LCS, for the 485
communications is 7. RS485 connection remains the same for all 7 devices.
Sigma_XT_signs_m3.5.docx
Page 6 of 14