Max Number of FPC-2 Units chained together is 3 using the power IN / OUT link. For additional units need to wire
separately. Power supply will need to consider what current is required to ensure all devices operate correctly.
Detection zone wiring
These terminals are for the connection of a conventional type 24V smoke detector or other another detection device
such as linear heat detection cable.
A 6K8 end of line monitoring resistor is fitted to these terminals. This must be removed and placed across the end
of the detection circuit wiring to provide open circuit monitoring for the detection cable.
Note: automatic detectors are polarity sensitive so polarity should be observed. If a short circuit take place over
the detection line (either by linear heat detector activation or smoke detector activation [470 Ohms] or by accident),
then the panel will immediately proceed to activation
Sounder circuit wiring
There is no dedicated Siren circuit on this
panel.
Using the Fire Relay a siren can be
connected.
The "FIRE" terminal on the FPC2 is a relay that
creates a closed circuit upon activation of the
panel. In cases where a sounder/strobe is
needed in the installation of the
system, it is connected at this terminal so as to
go off upon activation of the panel.