Installation
4
FirePro Aerosol Genrators must be selected in accordance with approved FirePro design
4.1
calculations and guidelines. FirePro Brackets must be installed using Bolts – Tec Screws will
vibrate loose in vehicle/marine installations.
FirePro units have a self-activation temperature of 300⁰C. Placement of units should be carefully
4.2
selected.
All cabling in the FirePro Installation MUST be Installed using min 0.75mm shielded Fire Rated
4.3
Cable
Power MUST be connected directly power supply OR Battery to ensure operation of the system.
4.4
6 – 30v DC. 5A fuse or circuit breaker to be installed on power supply.
Manual Actuator(s) where installed, placement is to be carefully considered – ensure that it is
4.5
easily accessible in case of emergency. Follow instructios for the installation of the FP-14053
switch.
Linear Heat Detection where installed, the system will activate automatically. Follow instructions
4.6
as per FP-09510 product manual.
Cable Requirements - All cabling in the FirePro
4.7
Installation MUST be done using 0.75mm shielded
Fire Rated Cable. Care taken to ensure that all
cables are isolated, and that RF shielding on cable is
stripped back to ensure that there is not accidental grounding. Cables are colour coded for easy
identification.
Extension Leads - Deutsch Plugs must be used to
4.8
ensure
water-proof
throughout the installation.
Incorrect installation may cause activation.
connections
Local Application Fire System
Colour
are
made
FP-08917
Circuit
Red
Power
Yellow
Activation
Green
Detection / Manual Switch
Rev 3.1
Page | 4