- ページ 11
煙警報器 Fireray 5000のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。Fireray 5000 17 ページ。 Motorised infrared optical beam smoke detector
14. Manual Fire and Fault Tests
After installation or cleaning, it is recommended that a manual Fire and Fault test is
performed:
Fire Test: Cover the Reflector slowly so that it takes longer than 5 seconds to cover. The
System Controller will signal Fire to the Fire Control Panel after the delay to fire has expired
(10s default)
Fault Test: Cover the Reflector completely within 2 seconds. The System Controller will signal
Fault back to the Fire Control Panel after the delay to fault has expired (10s default)
15. Remote Fire Test
It is possible to perform a Fire Test from the System Controller, to test the wiring to the Fire
Control Panel
NOTE: The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine
Maintenance per UL268-5
Detector Fire LED Test
Detector will signal Fire,
System Controller will stay
Normal.
Press
to exit
without performing the test
11
Relay/Controller Wiring Test
System Controller signals
'Fire' to Fire Control Panel
Press
or
to
exit