SATK20 & SATK30
Maintenance
Temperature probe replacement
Disconnect the probe cable, lightly folding the tab (C) and
extracting the connector (see page 17)
Unscrew the probe
Fit the new probe
Reconnect the connector respecting the only possible way
it can be inserted.
Replacing the valve actuator
Disconnect the actuator cable, lightly pressing the tab on
the connector and extracting it (see page 17).
Extract the fixing clip (D) and then the actuator.
Position the new actuator (E).
Insert the fixing clip, respecting the correct direction.
Reconnect the connector.
D
E
Replacing the valve obturator
Disconnect the valve actuator (see previous paragraph).
Extract the obturator, unscrewing the locking nut (F).
Replace the obturator and screw on the locking nut (F),
then insert the actuator.
Insert the fixing clip, respecting the correct direction
Reconnect the connector.
F
C
Replacing the DHW priority flow meter
Disconnect the flow meter cable by means of the
connector (see page 17).
Extract the flow sensor (G).
Position the new sensor.
Reconnect the connector respecting the only possible way
it can be inserted.
Replacing or cleaning the DHW priority flow meter turbine
Extract the flow sensor
Unscrew and remove the cartridge (H)
Remove any impurities present or change the cartridge if
necessary
Screw in the cartridge
Reposition the flow sensor.
When carrying out maintenance on the electrical system, for
the connections follow the diagram on page 16.
After concluding maintenance, refill the system and check the
operations described in the chapter "Commissioning" and
re-fit the cover.
For information regarding spare parts or other technical
information, please contact Altecnic.
Only genuine Altecnic re-placement components should be
used.
16
G
H