計測機器 CALEFFI 750714のPDF マニュアルをオンラインで閲覧またはダウンロードできます。CALEFFI 750714 16 ページ。 Direct heat meter

• Heating/cooling flow meter
11 - 12 Flow meter pulse input.
11 (blue wire)
12 (white wire)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
blue wire
blue wire
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
• Electric supply
blue wire
15 - 16 Centralised 24 V (ac) electric supply line
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
The 24 V (ac) electric supply line must only be used for heat
meters and must not be under the user's control.
blue wire
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
• Data centralisation
If centralised data transmission via BUS is used, the following
connection plan must be implemented:
17 - 18 RS-485 polarised transmission Bus
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
17 Tx (RS-485-B)
18 Rx (RS-485-A)
For the transmission bus, use 2 x 1 mm
twisted type. Note: Transmission polarisation must be fully
observed
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
• Enery pulse outputs - codes 755881/755882
2 - 3
Remote heating units totaliser output (kWh) (OC type)
1 - 2
Remote cooling units totaliser output (kWh) (OC type)
These outputs can be connected to our product code 755890
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
(remote energy totaliser) or a general supervisor.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Output specifications:
1 IMP = 1 kWh - open collector contact
Pulse duration: 120 ms
24 V (dc) - 50 mA
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Maximum frequency = 1 Hz
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
white wire
white wire
white wire
white wire
cable, preferably of the
2
• Additional pulse inputs 755825
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
E.g.: Heating water - Electrical energy - Gas
NOTE: The additional inputs are only enabled with codes 755825.
Connection must be with a voltage-free contact and the weight and unit
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
of measurement for the pulse must be indicated at the time of ordering.
E.g.:
1 pulse = 10 litres of heating water
1 pulse = 0,1 kWh electrical energy
1 pulse = 1 Nm
3
gas
6 - 7
3rd pulse consumption
5 - 6
4th pulse consumption
Minimum pulse duration: 120 ms
Maximum frequency = 1 Hz
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
• Digital input
The digital input must be with a voltage-free contact (class IB)
13 - 14 Connection to the auxiliary microswitch for the zone valve.
Note
- Each 7504 series appliance comes with a tamper-proof lead
sealing kit for the temperature probes and the plastic electronics
box.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Operating information
Accumulated energy is stored in a non-volatile memory device
(EEPROM) each time the unit of measurement is competed (1 kWh);
at the same time this increase results in updating of the display (see
"User information cycle").