OE 3010
VOLTAGE DETECTOR
3omA Differential Circuit-Breaker Tripping (RCDs) Test
Attention:
This test involves creating a fault current ( > 3omA at 23OVAC) between the phase and earth.
1. Connect the red test probe to the " + " jack and the black test lead to the " COM " jack.
2. Connect the red test probe to the phase and the black test probe to the earth terminal bar.
The tester indicates the voltage of the circuit connected.
3. Press the RCD test key. (The tester changes to RCD test mode and stops indicating the voltage of the circuit
connected.
4. The 3omA differential circuit breaker must trip if it is good.
Note: Test duration must not exceed 30 secs, and interval between tests must be more than 4 minutes.
Characteristics and range for use:
1. Voltage: 230V Ph/T
2. Fault current generated: > 30mA
3. Frequency: 50Hz – 60Hz ( +/- 5%)
MAINTENANCE
Replacing the Battery
Disconnect the tester from the circuit under test before battery replacement.
1. Remove the screws on the battery cover and remove the battery cover.
2. Replace the old battery with a new one of the same type.
3.Reinstall the battery cover and the screws.
Cleaning
Before cleaning, disconnect the tester from the circuit under test. Use moist cloth and mild detergent to clean the
tester. Never use abrasive or solvent.
After cleaning, do not use the tester until it is completely dry.
Storage
If you don't use the tester in a long period of time, you should remove the battery.
The tester should be placed in a dry place when not in use.
Disposal of this article
If you at some point intend to dispose of this article, then please keep in mind that many of its components consist
of valuable materials, which can be recycled. Please do not discharge it in the garbage bin, but check with your
local council for recycling facilities in your area.