2

3 .0 mounting instructions

Find a safe place and mount the disconnect where it conve-
niently fits, within clear line of sight and less than 50ft / 15m
from the pump. The product should be fixed using appropriate
screws; ensure you have the correct size for the box sizes. The
conduit / cable should be secured and protected against physi-
cal damage. Make sure the installation follows all local codes
and standards.
4 .0 conduit/cables termination
a
30 amps fused disconnect
The 30 Amp disconnect is provided with 4×25mm-32mm
knockouts (KOs), select the one that will be easiest to con-
nect the cable/conduit. Find the point of attachment for this
KO. Press the edge of a screwdriver against the selected KO's
stamped edge, opposite the point of attachment, and press (or
rap sharply if needed) to push the KO away from the enclosure.
Fused
Disconnects
PZ2/1×6
2,5 Nm MAX
35 mm
16-40 A 16mm
40-80 A 35mm
After correct size opening is achieved, insert the conduit/cable
connector into the opening from the outside box and secure it
using a connector locknut.
Note: Grounding bushing might be required, please refer to your local
code and standard.
b
60 amps fused disconnect
Cut holes in the enclosure at the desired location. The use of a
Greenlee Cutter is the preferred method, placing the punch of
the Greenlee Cutter on the inside of the enclosure and punch
through to the outside.

conduit connections

Metallic conduit – First secure the conduit connector onto
the conduit. Then secure conduit connector into the prepared
enclosure hole using the connector locknut. Then attach the
grounding bushing, having the proper size ground wire lug, over
the connection locknut.
caution
Bonding between the grounding bushing(s) and the
equipment grounding terminal must be included as
part of the installation procedure in accordance with
the local code.
Non-Metallic conduit – Secure conduit to the conduit connec-
tor either before or after the conduit connector is secured into
the prepared hole using connector locknut
Note: Grounding bushing is not required
o-ring
outside of
enclosure
conduit
Cu
2
1,8 Nm MAX
2
2,5 Nm MAX
2
enclosure
hole size
grounding
connector
bushing
locknut
(when used)