- ページ 2
コントロールユニット Acorn Engineering SFST-T-OT-CWB-ITGのPDF 設置、操作、メンテナンスの説明書をオンラインで閲覧またはダウンロードできます。Acorn Engineering SFST-T-OT-CWB-ITG 8 ページ。 Sfst series thermostatic mixing valve supply fixture
WARNING:
!
You are required to thoroughly read all installation
instructions and product safety information before
beginning the installation of this product.
FAILURE TO READ AND FOLLOW PROPER
INSTALLATION AND MAINTENANCE
INSTRUCTIONS MAY RESULT IN PRODUCT
FAILURE WHICH CAN CAUSE PROPERTY
DAMAGE, PERSONAL INJURY AND/OR
DEATH.
Acorn Controls is not responsible for damages
resulting from improper installation and/or
maintenance. Installation of this valve shall be in
accordance with Uniform Plumbing Code.
TO ENSURE ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
Properly design the system to minimize
Ÿ
pressure and temperature variations.
Implement an annual maintenance program
Ÿ
to ensure proper operation and temperature
setting of valve(s).
This valve is factory preset. However, it can
Ÿ
be adjusted. It is the responsibility of the
installer and or facility maintenance personnel
to make sure valve outlet temperature does
not exceed 115°F (46°C) after installation,
maintenance or repair.
Acorn Controls
Division of Acorn Engineering Company
Manual #7802-117-000
SFST Installation & Operation Manual
SUPPLIES REQUIRED:
(Not provided by Acorn)
1. Wall anchors, screws nuts and washers as
required.
2. Lead free solder and flux for sealing water
connections.
3. Pipe fittings.
4. 5/8" wrench and 1/8" Allen wrench.
!
IMPORTANT
Ÿ
Flush supply lines of all foreign material such as
pipe dope, chips or solder prior to connecting to
mixing valve.
Ÿ
To ensure proper installation, review the Manual
thoroughly to verify rough-ins before beginning
any work.
Ÿ
Installation and field adjustment are the
responsibility of the installer.
Ÿ
Maximum water pressure is 125 psi (8.62 bars).
Maximum inlet hot water temperature is 180°F
(82°C). Temperature adjustment range* is
90°C-115°F (32°C-46°C). Valve assembly must
be drained prior to being subjected to freezing
temperatures. Valve includes integral check
valves.
*In accordance with ASSE 1070 and ASSE 1069
PRESSURE
5
DROP
Cv
(34)
PSID (kPa)
4
FLOW RATE
1.8
GPM (LPM)
(15)
, A member of Morris Group International
®
10
15
20
30
(69)
(103)
(138)
(207)
5.7
7
8
9.8
(21.4)
(26.2)
(30.2)
(37)
™
45
60
(310)
(414)
12
13.8
(45.4)
(52.4)
Page 2 of 8
Date: 09/22/17