- ページ 13

ボイラー用品 Aerco 89030のPDF 技術指導をオンラインで閲覧またはダウンロードできます。Aerco 89030 14 ページ。 Condensate neutralization tank

Condensate Neutralization Tank User Instructions

OPERATION

The appliance condensate will flow through the neutralizing media, raising the condensate pH to
a level that will help prevent corrosion of the domestic drain and the public sewer system.

MAINTENANCE

Monitor the level of the neutralization media in the tank periodically. The pH can be checked after
the condensate has exited the tank or by removing the lid and taking a sample from the last
chamber before the outlet. Check the pH level every three months for the first year. Use a suitable
pH test strip paper or an electronic pH meter for precise measurement. The frequency of checking
the pH level can be reduced to every six months or every year depending on the readings obtained
compared to local water authority requirements. The neutralizing media should be replaced when
the pH level drops below the minimum level of the local water authority. For replacement media
contact your local AERCO sales representative.
Replacement neutralization media for KC, BMK, INN, Recon, MFC, and Modulex series
models is P/N 89031.
Replacement neutralization media for AM Series models is P/N 62801022.
At delivery, the replacement media comes in two clear plastic bags; a smaller one inside the
bigger (Figure 10). The larger bag consists of larger pieces of neutralization material, while the
smaller bag consists of smaller pellets of neutralization material. Replenish the tank with the larger
material, then sprinkle the smaller pellets on top.
Figure 10: Condensate Neutralization Tank Replacement Media (In Bags)

LIMITED WARRANTY

The unit is warranted against defects in materials and workmanship for one year.
TID-0074_0H
8/22/2022
Bag Containing
Larger Pieces
of Media
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Bag Inside
Containing
Smaller Pieces
of Media
Inside
Page 13 of 14