3 PRODUCT DESCRIPTION
The AMC-1040 is an all in one gas monitoring system incorporating a highly specific
electrochemical sensor from AMC's broad selection of available types. It serves to continuously
monitor the target gas (listed in Product Information Section). The monitor comes with the
following features (see Figures 1, 2 and 3).
1. POWER ON INDICATOR:
2. FAIL INDICATOR:
3. LOW ALARM INDICATOR:
4. HIGH ALARM INDICATOR:
5. POWER TERMINAL BLOCK:
6. TEST SWITCH:
7. LOW ALARM ADJUST:
8. HIGH ALARM ADJUST:
9. THREE CIRCUIT MINIATURE
SWITCH:
9. a) TOP ACTUATOR:
9. b) MIDDLE ACTUATOR:
9. c) BOTTOM ACTUATOR:
10. RELAYS:
11. TRANSFORMER:
12. AUDIO ALARM:
13. ANALOG OUTPUT:
14. ON-BOARD SENSOR:
AMC-1040 Monitor
Power is indicated by a green LED.
Sensor fail is indicated by an amber LED.
Low levels of gas are indicated by a yellow LED.
High levels of gas are indicated by a red LED.
For line voltage connections (120 VAC, 60 Hz.)
The test switch is provided to electronically simulate alarms
in order to test the low and high alarm indicators and relays.
Sets the Low alarm trip point.
Sets the High alarm trip point.
Each actuator on the miniature switch controls a different
circuit as shown in Figure 1. If the actuator is set in the UP
position, its corresponding circuit is ON. If the actuator is
set in the DOWN position, the circuit is OFF.
Provides a TEN minute time delay, when the switch is ON,
to eliminate unnecessary alarms caused by momentary
exposure to high alarm conditions.
Provides a FIVE minute time delay, when the switch is ON,
to eliminate unnecessary alarms caused by momentary
exposure to low alarm conditions.
Controls the audio alarm indicator. When ON, the buzzer
will activate when a high alarm condition occurs.
There are up to 3 DPDT relays which work with high alarm,
low alarm, and as an option fail.
Class II, step down transformer runs the internal circuitry at
low voltages.
When enabled, the buzzer will activate when a high alarm
condition occurs.
4-20 mA output 250 ohms load maximum.
Allows local detection of gas.