4.3 CABLE SIZES
For maximum noise rejection, each cable shield and metal conduit should be grounded at the
monitor. The following is a listing of maximum distances the transmitter may be located from the
monitor for various cable sizes.
WIRE
GAUGE
AWG
22
20
18
16
14
AMC-1044-T Monitor
CABLE LENGTH in FEET (meters)
3-Wire Transmitter
185 (56)
290 (88)
460 (141)
700 (214)
1110 (338)
6
2-Wire Transmitter
1000 (305)
1500 (457)
2500 (762)
3800 (1158)