- ページ 2

アクセサリー Diversa WOSSDU2-P-TWのPDF 技術データをオンラインで閲覧またはダウンロードできます。Diversa WOSSDU2-P-TW 4 ページ。 Wall switch occupancy sensor line voltage with neutral

Wiring Instructions
The WOS Series Line Voltage sensors are equipped with #14 AWG leads. Use appropriate sized wire-nuts to connect the wires to the
incoming load terminations.

Electrical Connections

Sensor Settings
Programming - IR / Manual Setting
Programming can be done either with the DIP switches and dials on-
board the device or with the WIR-3110 setting unit. For more details and
additional options, please see the "WIR-3110 Manual".
Detection (Dual or PIR Only)
When in operation, the sensor will detect initial motion using Passive
Infrared; once motion is detected the ADI-Voice is then is activated to work
alongside the PIR to maintain occupancy. The ADI-Voice can be disabled
on any dual tech sensors.
Automatic Timeout
By setting the timeout dial to maximum, the sensor will be put into automatic
mode which will adjust the time out automatically to maximize energy
savings and occupant comfort.
Smart Sensing
When vacancy occurs, sensitivity of the ADI-Voice technology transitions
from maximum to zero over an adaptively determined time period, based
on occupancy tendencies. During this period, ADI-Voice can turn the lights
back on immediately, even with no line-of-sight to the sensor, assuring the
best combination of user convenience and energy savings.
Energy consumption due to false triggers is minimized by the automatic
walk-through mode. This feature turns the lights off after 3 minutes if no
occupancy detection occurs after the first 30 seconds after initial turn on.
Ph. 877-873-2797
®
Details
WOSSDU1-P-TW
Neutral
Wht
Line
Blk
Blk/Wht
Load
Grn
Ground
(required)
WOSSDU2-P-TW
Neutral
Wht
Line
Blk
Blk/Wht
Load
Grn
Ground
(required)
www.DouglasLightingControls.com
Wall Switch Occupancy Sensor
Line Voltage with Neutral
Blu
Line
Blu/Wht
Load
Photo Sensing (-P)
When enabled, occupancy alone will not trigger the output state to on. If
occupancy is detected AND there is a deficiency of natural light, the output
is triggered on. An increase in natural light will not force the lights off but as
the ambient light level drops the lights will turn on automatically.
Multi-Level Photo Sensing (2-Pole w/ Photo Option)
Photo sensing on a 2-pole sensor can be configured to either restrict both
poles or the secondary pole only; if set to "Secondary Pole Only", the
primary pole will trigger based on occupancy, regardless of the photo
setting.
2018-10-16