- ページ 3
アクセサリー esera automation Multisensor 11132 Gen2のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。esera automation Multisensor 11132 Gen2 5 ページ。 Flush-mounted living area sensor
Art. No. 11132 Gen2
brightness calculation
Xsense in Volt, factor = 25600
Correction for operating voltage fluctuations: Xsense = (5 / VDD) * Xsense
Brightness (LUX) = (0,223V - Xsense) * Factor
Note on light sensor
the light sensor within the 1-Wire multi-sensor is suitable for detecting brightness or darkness, e.g. whether light is
on or off in a room, due to the installation position in the wall, flush-mounted in relation to the living area lighting
(ceiling). This behaviour is due to the installation position in the wall (flush-mounted). This sensor can only be
used to a limited extent to implement good brightness-dependent lighting control.
Sample program (PHP script for IP-Symcon)
Humidity values, dew point, brightness and operating voltage are calculated per script. For details see example
script in the shop.
9
Data output 1-Wire Controller / 1-Wire Gateway
For the 1-Wire Multisensor, the following measured values are calculated and output via the 1-Wire Controller / 1-
Wire Gateway. The dew point calculation is a function of the 1-Wire Controller / 1-Wire Gateway.
Important: Please assign article number 11133 to the 1-Wire Multisensor via Config Tool 3. This is the
only way to activate the correct library for this Multisensor generation.
Why assign article number 11133? The electronics of the 1-Wire Multisensor has been adapted to the
Multisensors with the article numbers 11134 and 11135. In order to ensure a distinction from the previous 1-Wire
Multisensors (11132 before 2019), article number 11133 has been assigned to the new library.
Data output:
1_EVT|12:27:40
1_OWD1_1|2008
1_OWD1_2|511
1_OWD1_3|4300
1_OWD1_4|1200
1_OWD1_5|80000
Further information on the possibilities and commands can be found in the current documentation for the 1-Wire
Controller / 1-Wire Gateway devices.
10
Integration in IP-Symcon / ESERA-Station
Via our website we provide ESERA IP-Symcon software modules for reading the 1-Wire Multisensor into IP-
Symcon via 1-Wire Controller / 1-Wire Gateway. Thus no scripts are necessary. Details can be found on the
ESERA website under "Compatible Controls/Centrals/IP-Symcon Integration".
https://www.esera.de/kompatible-steuerungen-zentralen/ip-symcon-integration/
For the conventional connection via 1-Wire Bus Coupler, the sensor values must be calculated according to
the specified formulas.
11
Integration in Loxone
Via the shop we provide an example project for reading the 1-Wire multisensor via 1-Wire Controller 1. Details
see here:
https://www.esera.de/kompatible-steuerungen-zentralen/loxone-integration/demo-1-wire-controller-1-loxone-
integration/
12
Integration in FHEM
For the integration into the open source automation software FHEM we provide a software module for reading
the 1-Wire multisensor via 1-Wire Controller / 1-Wire Gateway. This eliminates the need for evaluation scripts.
Details can be found on the ESERA website under "Compatible Controls - Central Units / FHEM Integration".
https://www.esera.de/kompatible-steuerungen-zentralen/fhem-integration/
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
=> Controller No._Module no. _Data set|Temperature (°C) Example: 20.08 °C
=> Controller No._Module no. _Data set|Voltage VCC (V)
=> Controller No_ Module no. _Data set|Air humidity (rH) Example 43,0%
=> Controller No._Module no. _Data set|Dew point (°C) Example: 12.00°C
=> Controller No._Module no. _Data set|Brightness (Lux) Example: 800.00 Lux
11132 V2.0 R1.0 Manual