- ページ 4
スイッチ esera automation 11220 V2のPDF ユーザーマニュアルをオンラインで閲覧またはダウンロードできます。esera automation 11220 V2 6 ページ。 8-fold switch module with button inputs for 1-wire bus
Apart from light buttons, any other pulse control signal can be used to
All three interfaces, the manual control mode interface, the 1-Wire interface as well as the button interface, work
in parallel on the outputs. For instance, a via the 1-Wire interface triggered output can be switched on or off either
manually or with button interface.
For instance, light switches can be connected to the button interface, in order to control the on/off light
commands. In this respect, normal light switches from all manufactures can be used.
Within the module, a µ-controller takes over the query of the buttons of the 1-Wire interface and the control of the
relays. The query of the buttons and the 1-Wire component is handled by flank control.
The status of the relays is output by the 1-Wire interface. It does not matter if push button interface, manual mode
or 1-Wire command (software) has been used.
9
Software / Control
The 1-Wire interface of the 8-Fold digital output 8/8 is being controlled by standard commands for the DS2408
module. Outputs connected by the button interface or manual control mode can be read back with the 1-Wire
Interface.
10
Control
by 1-Wire Controller / 1-Wire Gateway
The 1-Wire interface of
Outputs switched by the pushbutton interface or in manual mode can be read back by the 1-wire interface. The 8-
fold High Power switching module can be easily controlled by a 1-Wire Controller / 1-Wire Gateway. For this
purpose the following two commands are available.
10.1
Switching of an output relay
To switch a relay output, use the following command to set the selected output to 0 or 1.
Command: SET,OWD,OUT,OWD-Number,Output,Value
Example: set,owd,out,2,1,1 => OWD Number 2, output 2 will be switched to "on".
After switching the output latest status will be output as confirmation.
10.2
Switching of all output relays (Port)
Some applications require switching all outputs with one command. The following command sets all outputs of the
1-Wire module to a desired state. Using this command will overwrite the current output status. The 1-wire
controller / 1-wire gateway handles the command adaptation to the connected
The input value will be output as decimal value 0-254. Each relay output has a value, which is added up in each
case.
Input 1 = 1, Input 2 = 2, Input 3 = 4, Input 4 = 8, Input 5 = 16, Input 6 = 32, Input 7 = 64,
Input 8 = 128.
If, e.g. outputs 1, 3 and 5 should be switched to 1, add up the output values.
This example: 1 + 4 + 16 = 21
All other relay outputs will be set to 0. If all outputs should be set to 0, output value will be 0 as well.
Possible output values for 1-Wire digital outputs: 0 – 255
Command: SET,OWD,OUTH,OWD-Number,Output value
Example: set,owd,outh,2,15 => OWD Number 2, outputs 1 to 4 will be switched to "on".
After switching the output, latest status will be output as confirmation.
10.3
Data Output 1-Wire Controller / 1-Wire Gateway
For the 8-Fold Digital Output 8/8, the following data are output for binary / digital inputs (pushbutton interface) and
relay outputs. The input/output value will be output as decimal value 0-254. In a second data set output will be
with binary display (0 and 1). Each input and each output has a value, which is added up in each case.
Input pushbutton interface:
Input 1 = 1, Input 2 = 2, Input 3 = 4, Input 4 = 8, Input 5 = 16, Input 6 = 32, Input 7 = 64,
Input 8 = 128.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA-Automation or E-Service GmbH. Errors and technical modification subject to change. ESERA-Automation, E-Service GmbH 2018
www.esera.de
8-Fold digital output 8/8
11220 V1.0_R1.1 Manual 8-Fold Switch Module
trigger
is controlled by standard commands for the DS2408 module.
the outputs.
8-Fold digital output
8/8.
Page 4 of 6