F081
FAULT HARDWARE - CHECK-SUM
Data in the eeprom wrong, pay much attention please
Press button RES, verify TEMPERATURE, SETTING, MACHINE, DATA;
call the builder
F082
LOGIC SUPPLY (CN2) AND POWER SUPPLY (CN1) HAVE DIFFERENT PHASES
Verify that the supplies have the same fase
F083
REFERENCE CABLE WRONG TURNED
Turn reference cable: (CN1/3 WITH CN6/1 - CN1/4 WITH CN6/2)
F085
SEALING TIME HIGHER THEN MACHINE DATA "SEALING TIME"
Increase machine data sealing time (If 0 the controll is off).
F089
BAND BROKEN IF THE BANDS ARE PARALLEL CONNECTED
Verify the bands.
F090
SHORT CIRCUIT BETWEEN THE BANDS OR BETWEEN A BAND AND GROUND IN THE
CASE OF HIGH CURRENT
Verify bands, verify power connection between thermoregulator and bands
F092
POWER PART FAILURE
Reset the thermoregulator; if problem persist call the supplying
F093
BAND BROKEN DURING A SEAL
Verify power on the transformer, Verify voltage on CN/1 CN/2 connector, verify breaking of power cables,
verify breaking of bands.
F094
REFERENCE SIGNAL CABLE FROM BANDS IS INTERRUPTED
Verify the connection of reference signal cable from band ( CN6/1 - CN6/2 )
F095
MAIN SUPPLY SYNCRONISM DOES NOT MUCH MACHINE REQUIREMENTS
Internal hardware problem, call the supplying builder
F096
FAULT V-I TOO HIGH
Saturation of the voltage circuit, verify connection, probable break of one seal, if seals in parallel.
F097
PARTIAL SHORT CIRCUIT BETWEEN THE BANDS
Verify bands into machine probably not perfectly isolated.
If the problem persist repeat burn-in procedure or do calibrating.
To reduce the problems increase machine data partial short circuit
F099
FAULT GENERIC
call the builder
THERMOSALD ISC – MANUAL QUICK START
Manual cod.: 3ES080x_V5.1_QS_EN
Includes all previous models
Page Nr.
19
Rev. 2010 / 03
Tot. Nr . 20