2180 Air Relief Valve Repair Kits
Testing
The opening pressure of this valve may indicate differently depending
on the test equipment, instrumentation and air supply used. Where
possible the valve should be tested using identical conditions and the
same equipment as will be found on the system to be protected.
When this is not practical the test set-up should, as closely as
possible, approximate the conditions of the system to be protected.
Additionally the calibration of your test system should be checked
against your actual system by comparing the opening pressure of the
same relief valve on both systems.
1. Ensure that your air supply is rated to at least 100 PSI and that at
least 250 SCFM of air flow is available. If the air supply flow rate is
much less than the rated flow rate of the relief valve, the relief valve
will appear to relieve at a lower pressure than the rated value. This
discrepancy arises because the relief valve is a spring device that is
designed to lift slightly before the set relief (opening) pressure, but
will not flow a significant volume of air until the air reaches the
opening pressure. If the SCFM flow rate is low the air relief valve will
relieve a volume of air at lift pressure that cannot be made up by the
supply source, therefore the tester will not be able to reach the
opening pressure setting. In this situation the maximum pressure
read on the tester pressure gauge will be the initial lift pressure and
not the rated opening pressure.
All test equipment should be rated suitable for use with
high pressure.
2. Ensure that all supply lines and connections are at least ¾".
3. Ensure that all relevant instrumentation is correctly calibrated.
The most accurate results will be obtained when the relief valve to be
tested is connected to an accumulator or air receiver tank such that
the dynamic effect of the compressor system is reduced. Failure to do
so may result in an indicated opening pressure lower than the actual.
4. Screw the pressure relief valve to be tested into a 2" port on your
test system using pipe sealant on the air relief valve threads.
5. Open supply pressure isolation valve and allow air receiver tank
pressure to rise.
8
877.582.3569
2180 AIR RELIEF VALVE RK