OPERATION
OPERATION
fan k-factor
k = 70

5.6 Adjustable parameters

Parameter
Modbus
ON or OFF
Modbus
1...247
address
Modbus
7200, 9600, 14400, 19200, 38400, 57600
baudrate
Modbus
none, even, odd, none_2_stop_bits
parity
Unit
Pa and m³/h or InH
Operating
Measuring mode or control mode
mode
Differential pressure ΔP [Pa] or [InH
Parameter
Volume flow V [m
Chracteristic
curve linear or square root
Volume flow calculation according to: V = k · √Δp
with: V = Volume flow in [m
K-factor:
volume flow display indication up to 999,999 [m
measuring mode and control mode
differential pressure from 0 % p to 100 % of measuring range
Setpoint
volume flow from 0,5 % up to 100 % of measuiring range,
k-factor is considered
Output
0...10.0 V dc
voltage
P-gain
0...1,000
I-gain
0...100.00
positive/(heating): Control deviation = set value – actual value
The output increases when: Set value > actual value
Control
characteristic
negative/(cooling): Control deviation = actual value – set value
The output increases when: Actual value > set value
12
Doc.-no.: DPC200-MOD_02_EN
If selected parameter = volume flow
than follows the additional input for the k-factor
Button B1: reset value
Button B2: set value
Button B1: confirm value, display flashes once
Press button B2 to get to the next menu item
Selection or parameter range
0 and cfm
2
/h or cfm]
3
k = flow factor, adjustment range: 1...10,000
Δp = differential pressure in [Pa] or [InH
O]
2
/h] or [cfm]
3
O]
2
/h or cfm] in
3
Issue: 08/2019
default
ON
1
19200
none
Pa and m³/h
measuring
mode
differential
pressure ΔP
[Pa]
linear
K = 70
Set = 8888
Set = 8888
U
= 10 V dc
out
P = 50
I = 3.15
positive /
heating