- ページ 9
コントローラー Arthur Grillo DPC200-MODのPDF 設置および操作マニュアルをオンラインで閲覧またはダウンロードできます。Arthur Grillo DPC200-MOD 18 ページ。 Differential pressure / volume flow controller
5.2 Menu structure
∆P control mode
∆P = 150 Pa
Press B1
about 2 seconds to start menu.
menu
Press B2
button
Press B1
modbus
on
>off<
button
Press B2
button
Press B1
unit
metric
button
operating mode
measuring mode
Press B2
button
Press B1
parameter
diff. pressure
button
Press B2
button
Press B1
characteristic
linear
button
Press B2
button
Doc.-no.: DPC200-MOD_02_EN
modbus
>on<
off
Press B2 button
Press B1: Reset
Press B2: Select
modbus address
Press B1: Confirm
1
Display flashes once
Press B2 button
Press B1: choose among
modbus baud rate
7200, 9600, 14400,
9600
19200, 38400, 57600
Press B2 button
Press B1: choose
modbus parity
among none, even, odd,
none
none_2_sop_bits
unit
imperial
Press B2 button
Press B1 button
operating mode
control mode
Press B2 button
parameter
volumne flow
diff. pressure
Press B2 button
Press B2 button
fan k-factor
k = 70
Press B2 button
characteristic
square root
Press B2 button
back and confirm
Press B2
menu
Press B1
parameter
button
setpoint
50 pA
Press B2 button
output voltage
U = 10,0v
Press B2 button
p - parameter
50
Press B2 button
i - parameter
3,15
Press B2 button
controling mode
positive / heating
Press B1 button
to leave menu
button to stay in the menu
Issue: 08/2019
OPERATION
parameter
volumne flow
Press B2 button
Press B1: Reset
Press B2: Select
fan k-factor
Press B1: Confirm
k = 70
Display flashes once
Press B2 button
Press B1: Reset
Press B2: Select
Press B1: Confirm
Display flashes once
Press B1: Reset
Press B2: Select
Press B1: Confirm
Display flashes once
Press B1: Reset
Press B2: Select
Press B1: Confirm
Display flashes once
Press B1: Reset
Press B2: Select
Press B1: Confirm
Display flashes once
Press B1
controling
negative / cooling
button
∆P control mode
∆P = 150 Pa
9