1. General Information (Use this in conjunction with respective Installation Guide):
Altronix AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA and
AL1002ULADAJ are very versatile devices. They can be used with or without specific synchronization modules
provided by some manufacturers. Multiple units can be synchronized by using either the built-in sync mode or a
external synchronization module. Please note, that only notification appliances with synchronization capabilities
can be synchronized. Contact signal manufacturer for more detailed information. Units can operate with either
one (1) or two (2) outputs from the FACP.
2. Class A, Style Z and Class B, Style W, Y Hookups:
Units can be used with the outputs configured for:
• Two (2) Class A, Style Z (Fig. 2a ).
• Up to Four (4) Class B, Style W, Y
Fig. 2a
SW2
SW1
ON
ON
+ OUT1 --
1
1
Fig. 2b
SW2
SW1
ON
ON
+ OUT1 --
1
1
- 2 -
+ OUT2 --
+ OUT3 --
Two (2) Class A, StyleZ
Hookups
+ OUT2 --
+ OUT3 --
2.2K
EOL
One (1) Class A, StyleZ
two (2) Class B, Style W, Y
Hookups
• Two (2) Class B, Style W, Y and
one (1) Class A, Style Z NAC circuits (Fig. 2b).
+ OUT4 --
NAC Loop 1 starts on Output 1 and terminates on
Output 3. Switch SW1, when ON, provides proper
termination for this loop. NAC Loop 2 starts on
IN1+ IN1--
IN2+
IN2--
Output 2 and terminates on Output 4, SW2 must be
RET1+ RET1--
RET2+
turned ON for proper termination.
Please make sure that all the DIP switches for
corresponding outputs are set the same way.
From
FACP
NAC1
Return
to FACP
For combination of two (2) Class B, Style W, Y and
+ OUT4 --
one (1) Class A, Style Z circuit, only one (1) switch
(SW1 or SW2) must be turned ON, terminating
Class A circuit only.
IN1+ IN1--
IN2+
IN2--
RET1+ RET1--
RET2+
2.2K
EOL
C "DRY1" NC
UPPER TERMINALS
RET2--
C "DRY2" NC
LOWER TERMINALS
Return
to FACP
From
FACP
NAC2
C "DRY1" NC
UPPER TERMINALS
RET2--
C "DRY2" NC
LOWER TERMINALS
02 ULADA Application Guide