- ページ 2

電源 Cutler-Hammer MP-3000のPDF 使用方法をオンラインで閲覧またはダウンロードできます。Cutler-Hammer MP-3000 2 ページ。

Page 2
4. Replace the front cover and the four bolts to secure
the front cover.
WIRING
See Figure 2 for electrical connections.
1. Note that the unit has no ON-OFF switch – identify
some external means of removing the dc supply.
2. Connect the ac load to the terminals labeled AC OUT.
Either terminal can be connected to ac common.
3. Connect the negative dc supply lead to the terminal
labeled DC GND. Note: This terminal is not
connected to safety or case ground – it can not
provide a dc circuit ground.
4. Connect the positive dc supply lead to the terminal
labeled DC IN.
Figure 1. Outline Dimensions
NOTE: If a single IQ DC Power Supply is being used to
power both an IQ 1000 II and a URTD or other load
together, contact Cutler-Hammer Technical Assistance
for specific wiring instructions.
Cutler-Hammer
Five Parkway Center
Pittsburgh, PA 15220
Style No. PRELIM Effective 07/98
Printed in U.S.A.
Figure 2. Connection Diagram
RECOMMENDED CONNECTIONS
Use #14 AWG conductors, copper only.
Tighten terminals to 7 pound-inches.
OPERATION
Dc voltage may be applied to the IQ DC Power Supply by
any number of methods. It will start reliably with a 250
Vdc step input from a contactor or with a slow ramp from
a dc power source.
When dc power is applied, the unit will wait approximately
21 seconds with both LED's on. After activating the ac
output the unit will blink the LED labeled D1 and may or
may not indicate an overload briefly when starting. The
various LED indications are listed below. Normal
conditions have D1 blinking and D2 dark; but D2 may
blink sporadically without indicating a problem.
AVERAGE-CURRENT OVERLOAD
D1 and D2
blinking alternately
PEAK CURRENT OVERLOAD OR OUTPUT SHORT
D1
blinking
D2
blinking ON or OFF sporadically, or ON
continuously.
To recover, remove or lighten load and wait two (2)
minutes for the start cycle to begin.
FOR TECHNICAL ASSISTANCE CALL 1-800-809-2772
OR VISIT http:\\www.ch.cutler-hammer.com/pmp
I.L. 17286B