- ページ 10

サーモスタット AKO 226.0320 SeriesのPDF 取り付けと点検の手順をオンラインで閲覧またはダウンロードできます。AKO 226.0320 Series 10 ページ。 Temperature regulator selfactuated, three-way temperature regulator with interior thermostat, balanced, with flange connections

AKO 226.0320 Series 取り付けと点検の手順
Mounting and Servicing Instructions
AKO Temperature Regulator selfactuated
12.2 Installation of thermostat
Assembly is executed in vice versa order. In case of control valves with manual
override, it has tube ensured that the tips oft he thermostat fit in the groove of the pressure plate
oft he valve cover. If they do not fit, the plates have to be bent carefully in order to make the
tips fit in the groove.
Fit the valve cover with new o-ring when necessary and tighten the bolts with torque wrench ca.
30 Nm.
If a thermostat with different temperature range has been fitted, replace the type label by a new
one showing the correct
12.3 Testing the function of the manual override
- open lock nut (pos. 10)
- turn the adjustment bolt (pos.9 clockwise for 10 mm by means of the wrench
(pos.8). In case the thermostat blocks or sticks, open the bolts (pos.5) and move the
valve cover until the drag disappears.
-bring the adjustment bolt in its original position and fix the lock nut.

13. REACh-Declaration

Declaration to regulation EC 1907/2006 concerning the Registration, Evaluation,
Authorisation and Restriction of Chemicals (REACh)
By the REACh-Regulation, the company AKO Regelungstechnik GmbH & Co. KG is only
affected as a downstream user. Responsibilities due to the production and Marketing of
substances / chemicals for pre-registration or registration are not applicable for us.
As a downstream user we will fulfil all requirements according to REACh.
Friedrich-Sertürner-Straße 14 • D-51377 Leverkusen • Tel.: +49 (0) 214 / 840599-0 • Fax: +49 (0) 214 / 840599-29
AKO Regelungstechnik GmbH & Co KG
eMail: [email protected] • Web: http://www.ako-regelungstechnik.de
10