- ページ 8
コントロールユニット Doepke Dupline DRO 4cのPDF 取扱説明書をオンラインで閲覧またはダウンロードできます。Doepke Dupline DRO 4c 12 ページ。 Shutter control unit
Doepke
Example:
The priority drive direction in the event of a bus fault ("UP", "DOWN" or no movement)
can also be preset for all relays with the hand encoder depending upon the A-B bridge.
Normally this bridge is inserted and the priority direction is "UP" (channel setting "1"). If
"0" is set, the DRO 4 will - in the event of a bus fault - activate the drive direction "DOWN"
provided the bridge is in place.
If the A-B bridge is removed, the DRO 4 will not activate the motors when a bus fault oc-
curs.
9. Putting into Service
9.1. Connections
Only an authorized expert is allowed to carry out the installation. When installing, the
connection diagram has to be observed. All conductors that shall be connected have to
be free of voltage. Following table shows the connections:
Terminal
Description
1.1
Motor 1 output UP („↑")
1.5
Motor 1 output DOWN („↓")
2.1
Motor 2 output UP („↑")
2.5
Motor 2 output DOWN („↓")
3.1
Motor 3 output UP („↑")
3.5
Motor 3 output DOWN („↓")
4.1
Motor 4 output UP („↑")
4.5
Motor 4 output DOWN („↓")
A-B
Jumper fitted: Preferred di-
a
4.4/4.8
rection
Not fitted: No movement
1.4
0 VDC operating voltage
a. On bus fault - please see chapter 8 "Coding".
Short circuits between Dupline signal conductors and the 24 V operating voltage or con-
nections to the grounding lead to malfunction and are not allowed. The correct polarity
of operating voltage and Dupline signal conductors has to be ensured.
In order to meet the requirements for protective low voltage, VDE 0100, Part 410, should
be observed and put into practice during installation.
When connecting please observe that the maximum torque of the terminals of 0.6 Nm
3931270/05/12/B - The right to make technical changes reserved!
8
UP
Motor 1
G6
Motor 4
L5
„Up" or „Down"
Wrong
DOWN
G7
P1
Terminal
1.2
Phase input motor 1 (L
1.6
Phase input motor 1 (L
2.2
Phase input motor 2 (L
2.6
Phase input motor 2 (L
3.2
Phase input motor 3 (L
3.6
Phase input motor 3 (L
4.2
Phase input motor 4 (L
4.6
Phase input motor 4 (L
1.3
Dupline signal conductor - (Dupline-)
1.7
Dupline signal conductor +
(Dupline+)
1.8
+24 VDC operating voltage
Right
UP
DOWN
M3
M4
H7
H8
Description
)
IN1
)
IN1
)
IN2
)
IN2
)
IN3
)
IN3
)
IN4
)
IN4